Product Details for GENT Vigilon 4 Channel Input/Output Interface (No Enclosure) (S4-34450)
The GENT S4-34450 is a loop powered interface designed for use with Vigilon fire alarm system control panels. This interface unit features 4 input / output channels which can be used to control services within a building. No enclosure. Interfaces are used to link the fire alarm system to other plant management devices such as sprinklers and security systems. They can also be used to link to a zone of conventional detectors.
The Vigilon system can accommodate a high capacity of single channel interfaces on the loop operating both inputs and outputs. The loop powered 4 channel interface range has individually sectored outputs with channel 1 set as a loop powered zone module. All interfaces are seen by the panel as one address although each input/output can have a separate label displayed at the panel.
Key Features of the S4-34450 |
|---|
|
> Loop-powered devices reducing cost of installation and maintenance
> Individual addresses to maximise information and flexible cause and effect > Each device with EN54-17 short circuit handling for enhanced system integrity > Comprehensive range of functionality in each device variant to simplify system design > Complete range of mounting enclosures and accessories > Options to connect conventional fire detectors such as flame and beam detectors > Certified to EN54-17 and EN54-18 |
| Brand | GENT |
|---|---|
| Manufacturer Part No. | S4-34450 |
FAQ’s for GENT Vigilon 4 Channel Input/Output Interface (No Enclosure) (S4-34450)
Product Specification for GENT Vigilon 4 Channel Input/Output Interface (No Enclosure) (S4-34450)
| Model: | S4-34450 GENT 4 Channel Interface (input/output) (no enclosure) |
| Dimensions: | W:90mm x H:93mm x D:23mm |
| Operating temperature: | -10ºC to 60ºC |
| Relative humidity (non condensing): | Up to 95%, Temperature 5ºC to 45ºC |
| Device load factor: | Load Factor 14 switch inputs = 1 (max. 200/loop) 1-4 relay outputs = 2 (max. 200/loop only 8 individually sectored) Zone Input = 26 (max. 30/loop) Every LED output = +5 (max. 100 LED outputs/loop) |
| Panel compatibility: | Compatible with Loop = V3.93 / V4.35 and Main Control Card = V3.94 / V4.37 |
| Approvals: | Approval EN54-17:2005 and EN54-18:2005 |
| Weight: | 100g |