Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

SKU
ZX432-2P
£60.44 £50.37
Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)
<span style="color: Chocolate;">Limited Stock</span> Limited Stock

Product Details for Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

The Ziton ZX432-2P is a wireless, polar white, addressable multi-sensor head, capable of operating in optical, temperature or multi-sensor, optical/heat modes. Works with ZR401-3 radio base (sold separately).

The ZX432-2 detector is controlled from the main control panel via a wireless base and loop wired radio interface module allowing both wireless and hardwired devices to be seamlessly located and controlled from the same wiring loop. Every wireless device controlled through the radio loop module, is assigned its own IDENT address with which the main control panel communicates, providing the same system facilities as directly wired devices.

Fast response to a wide range of fires

Designed to provide the earliest response to a wide range of fire types in locations where hard wiring is not an option, ZX432-2 detectors combine optical smoke sensing and thermal monitoring to provide an accurate warning of fire. Smoke sensing may be isolated for areas where ambient smoke may exist at certain times of the day, or used on a day night basis in premises where heat only is required whilst the building is occupied.

System operation

Temperature and smoke sensitivity may be set by a selection of switches located in the base of the ZX432-2. Calibration and self-testing are carried out automatically.

Removal or replacement of an incorrect sensing devices are identified by the system and details displayed at the main control panel. Sophisticated auto contamination adjustment compensates for any long-term drift in performance caused by dirt entering the sensing chamber.

For ease of removal, ZX432-2 detectors plug into the radio base by a simple twist and lock action.

Certification

The ZX432-2 temperature response meets the requirements of European Standard EN54 Part 5 (settable to class A or class B), with smoke sensitivity complying with EN54 Part 7. The ZR432-2 is approved to EN54:5, EN54:7 , and carries CPD certification.


Key Features of the ZX432-2P

> Polar white
> Replacement detector head only - no radio base/battery pack included
> No external aerials
> Dual battery supply via base
> Full device status monitoring – power sources, head removal and device tamper
> Senses both smoke and heat

More information about Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

More Information
Brand Ziton
Manufacturer Part No. ZX432-2P
Primary Power Source Replaceable Batteries (Alkaline)
System Type Wireless
Protocol Compatibility Ziton
Sensor Type Combined Optical and Thermistor
Detectable Medium Smoke, Heat
Warranty 2 Years
Write Your Own Review
You're reviewing:Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)
Your Rating

Datasheets and Manuals for Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

FAQ’s for Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Ziton ZP Wireless Multisensor Detector (Head Only - Radio Base Not Included) (ZX432-2P)

Code: ZX432-2P
Description: Ziton Wireless/Radio Multi-sensor (optical/heat) Head - works with ZR401-3 base & battery pack, polar white
Dimensions: Dia:106mm x H:75mm
Compatible products: 11510-ZT: ZPL1-1 address label 1001-1127
11520: ZPL1-2 Add.Label 2001-2127
11530-ZT: ZPL1-3 address label 3001-3127
00540-ZT: ZPL1-4 address label 4001-4127
Status indication:
Red alarm LED
Wireless frequency:
868 MHz
Power supply: Batteries in base, 3 VDC
Compatibility: All ZP addressable systems via RLM
Area coverage: Smoke element - <100m² Heat element - < 50m²
Monitoring: Continuously self-checking
Detection principle: Smoke element - Photoelectric light scatter Heat element - Thermistor
Addressing: Unique address embedded
Operating temperature: -10 to +60°C
Storage temperature: -20 to +70°C
Relative humidity: 10 to 95% noncondensing
IP rating: IP32, indoor
Material: Moulded ABS
Mounting: Surface
Colour: Polar white
Regulatory: CE,​ CPR,​ REACH,​ RoHS compliant
CPD,​ EN54-5,​ EN54-7 certified
Weight: 350g (including base & batteries)