Ziton Galvanic Isolator Unit for 670 series conventional systems

SKU
GBX2000
£366.60 £305.50
Ziton I.S. Isolated Barrier For Conventional Systems (GBX2000 )
Available to Order This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.

Product Details for Ziton Galvanic Isolator Unit for 670 series conventional systems

The Ziton GBX2000 is a galvanic isolation barrier selected specifically for use between an Intrinsically safe conventional zone and a zone-monitor.

Every GBX2000 (4 terminals) functions like a "DC current isolator" with reverse polarity protection. The input and output are galvanically isolated from each other. It is designed for the connection of fire detectors, smoke detectors, temperature sensors, etc. A detector's increased current range and the higher accuracy allow for differentiation between normal operation, fire alarm, lead breakage and short circuit currents in the safe area. In many cases they may also be used for controlling I/P converters. A separate power supply with auxiliary power is not required. Due to the input voltage limiting of 24 V, the maximum voltage output is 21 V.


Key Features of the GBX2000

> Approved with the IU2055 zone monitor unit
> Output EEx ia IIC
> Device installation permissible in zone 2
> Polarity reversal protected
> Accuracy 1%
> EMC acc. to NAMUR NE 21
> Up to SIL2 acc. to IEC 61508

More information about Ziton Galvanic Isolator Unit for 670 series conventional systems

More Information
Brand Ziton
Manufacturer Part No. GBX2000
Write Your Own Review
You're reviewing:Ziton Galvanic Isolator Unit for 670 series conventional systems
Your Rating

Datasheets and Manuals for Ziton Galvanic Isolator Unit for 670 series conventional systems

FAQ’s for Ziton Galvanic Isolator Unit for 670 series conventional systems

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Ziton Galvanic Isolator Unit for 670 series conventional systems

Code: GBX2000
Description: Ziton I.S. Isolated Barrier for Conventional Systems
Dimensions: W:20mm x H:107mm x D:115mm
Operating voltage: 4 to 35 VDC
Inputs/Outputs (not intrinsically safe):
Current: 0 to 40 mA
Power loss: at 40 mA and Uin < 22 V: 700 mW at 40 mA and Uin > 22V: 1.2 W
Inputs/Outputs (intrinsically safe): Voltage: for 4 V < Uin < 24 V: >= Uin - (0.37 x current in mA) - 1.0 for Uin > 24 V: = 21 V - (0.36 x current in mA)
Short-circuit current: at Uin > 24 V: >= 65 mA
Transfer current: <= 40 mA
Ambient temperature:
-20°C to +60°C
Group, category, type of protection: II (1) G D [EEx ia] IIC (-20°C <= Tamb <= 60°C)
Type of protection [EEx ia]: Explosion group: IIA IIB IIC
External capacitance: 2.9 µF 0.82 µF 0.107 µF
External inductance: 33 mH 18 mH 4.3 mH
Mounting type: DIN rail
Regulatory: CENELEC/ATEX certified
Weight: 100g