SKU
MKII-HF/CS90
£15.35
£12.79
Zeta Fyreye MKII Conventional CS 90°C Fixed Heat Detector (MKII-HF/CS90)
- Buy 10 for £14.88 £12.40 each and save 3%
- Buy 20 for £14.64 £12.20 each and save 5%
Available on Backorder
This item is not currently in stock, but it is available to backorder. Contact us for lead time.
Product Details for Zeta Fyreye MKII Conventional CS 90°C Fixed Heat Detector (MKII-HF/CS90)
The Zeta Fyreye MKII-HF/CS90 is a Conventional Fixed High-Temperature Heat Detector with a single thermistor arrangement that gives an alarm at a temperature of 90°C.
The detector will work with most modern fire alarm control panels, and comes supplied with a locking grub screw to prevent unauthorised head removal.
There are 4 types of mounting base available - standard or deep and with or without diode. Ideal for use with the Zeta Infinity range of conventional fire alarm control panels.
Key Features of the MKII-HF/CS90 |
|---|
|
> Conventional High Heat Detector
> Fixed 90°C temperature > Designed to meet EN54 requirement > Lockable to base to stop unauthorised removal > Remote LED output > Compatible with all Fyreye MKII bases |
| Brand | Zeta |
|---|---|
| Manufacturer Part No. | MKII-HF/CS90 |
| Product Series | Zeta Conventional |
| Primary Power Source | 24V DC |
| System Type | Conventional |
| Sensor Type | Thermistor |
| Detectable Medium | Heat |
| Colour | White |
| Warranty | 2 Years |
Write Your Own Review
FAQ’s for Zeta Fyreye MKII Conventional CS 90°C Fixed Heat Detector (MKII-HF/CS90)
No questions yet. Be the first to ask the question!
Product Specification for Zeta Fyreye MKII Conventional CS 90°C Fixed Heat Detector (MKII-HF/CS90)
| Product code: |
MKII-HF/CS90 |
| Description: | Zeta MKII Conventional Fixed High Heat Detector (CS) |
| Detector class: | Fixed Heat only |
| Dimensions (with base): | 100mm x 48mm |
| Design standard: |
EN54 part 5 |
| Approval: |
DIFT |
| CPD No.: |
0845-CPD-232.1701 |
| Operating voltage: |
9 - 33 VDC |
| Quiescent current: |
40μA |
| Alarm current @ 24 VDC |
34 mA |
| Operating temperature: |
-10°C to +80°C |
| Min. continuous temperature: |
0°C |
| Max. humidity: |
95% RH non-condensing |
| Alarm condition: |
Fixed heat trigger @ 90°C |
| Coverage: |
50m2 |
| IP rating: |
IP43 |
| Start up time: |
10 seconds |
| Weight (with base): | 75g (133g) |