SKU
IN6
£201.34
£167.78
Zeta Infinity8 6 Zone Conventional Fire Alarm Panel (IN6)
Available to Order
This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.
Product Details for Zeta Infinity8 6 Zone Conventional Fire Alarm Panel (IN6)
The Zeta Infinity8 6 Zone Conventional Fire Control Panel (IN6) is housed in an attractive, flame-retardant ABS enclosure and uses a switch-mode power supply. This model has 4 sounder circuits. The front cover is removable, allowing ease of access for cable installations. Space for up to 3Ah batteries. Meets all requirements of EN54 parts 2 & 4.
This panel can also be ordered with a metal back box that accommodates up to 7Ah batteries within the panel housing. (see product IN6/M)
Key Features of the IN6 |
|---|
|
> 6 Zones
> Access via password > One man test facility > Disablement facility for zones & sounders > Space for up to 3Ah batteries > Sounder delay option 4 sounder circuits > Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies > Complies with EN54 parts 2 & 4 |
| Brand | Zeta |
|---|---|
| Manufacturer Part No. | IN6 |
| Product Series | Zeta Conventional |
| Primary Power Source | Mains Powered (230V) |
| System Type | Conventional |
| Number of Zones | 6 |
| Colour | Grey |
| Warranty | 2 Years |
Write Your Own Review
FAQ’s for Zeta Infinity8 6 Zone Conventional Fire Alarm Panel (IN6)
No questions yet. Be the first to ask the question!
Product Specification for Zeta Infinity8 6 Zone Conventional Fire Alarm Panel (IN6)
| Product code: |
IN6 |
| Description: | Zeta Infinity8 6-Zone Panel |
| Dimensions: | 371mm x 302mm x 93mm |
| Mains voltage: |
230V AC +10% / -15% @ 50/60 Hz |
| System voltage: |
24V DC (Nominal) |
| Zone voltage: |
21V DC (Nominal) |
| Sounder Alarm Output: |
4 x 150mA @ 24V DC |
| Fault Relay: |
1 x Volt Free Relay, SELV @ 1A Max |
| Zone capacity: |
32 devices per zone |
| Remote sounder operation: |
Via N/O contact connected to Class Change |
| Sounder activation delay: |
0 to 10 minutes in 1 minute increments |
| Zone end of line: |
1N4002 Diode (Cathode stripe to zone +ve) |
| Sounder end of line: |
10K resistor |
| Charger voltage: |
27.6V |
| Battery cut off: | Battery voltage less than 20V |
| Battey internal resistance limit: | 0.9 ohm |
| Max. battery space: | 2 x 3.4 Ah, 12 Vdc sealed lead acid |
| Weight: | 3 kg (excluding batteries) |