Product Details for Signaline LocatorPlus-EN Linear Heat Detector Controller (SLP-002)
The Signaline LocatorPlus-EN (SLP-002) is a dual zone module for monitoring up to 2 zones of Signaline FT-EN linear heat detector cable. If an overheat/fire situation triggers either zone of the cable, this unit automatically calculates and displays the distance along the cable, in feet and metres, to the alarm point. The 2 zones can operate independently of each other, or in interlock mode, and a separate alarm and normally conducting fault output are provided for each zone. Install between the Signaline FT-EN Linear Heat Detection cable and a conventional or addressable fire alarm control panel. It has power, fault and alarm lights, as well as volt free outputs for fault and alarm corresponding to each zone. It may also be connected to an industrial process control system using the 2-wire RS-485 Modbus RTU/ASCII output.
Approved to EN54 part 28. Each zone is able to monitor 1000m of LHD cable, enabling the single unit to cover a vast detection area.
Key Features of the SLP-002 |
|---|
|
> Compatible with Signaline FT-88-EN, FT-78-EN LHD cable
> EN54-28:2016 approved > Independent or interlocking modes > Monitors 2 zones of up to 1000m of LHD cable each > IP65 rated > Alarm temperature: 78°C, 68°C, 88°C > Suitable for Safe areas > ActivFire, UL EN, CE approved |
| Brand | Signaline |
|---|---|
| Manufacturer Part No. | SLP-002 |
FAQ’s for Signaline LocatorPlus-EN Linear Heat Detector Controller (SLP-002)
Product Specification for Signaline LocatorPlus-EN Linear Heat Detector Controller (SLP-002)
| Product description: | Signaline LocatorPlus-EN Dual zone monitor module |
| Dimensions: | W:120mm x H:180mm x D:60.5mm |
| IP Rating: |
IP65 |
| Finish: | Light grey with clear lid. Orange faceplate |
| Display: | 2 line, 16 character backlit display with zone status |
| Approvals: | EN54-28:2016, UL File no.: S24913 |
| Operating voltage: |
12 / 24 / 36Vdc |
| Operating current: |
<15mA / <7mA / <5mA |
| Alarm current: |
<40mA / <23mA / <15mA |
| Operating temp. range: |
-20°C to +50°C (-4°F to +122°F) |
| Terminal blocks: |
5mm Rising Clamp |
| Rating: | 16A |
| Wire size: |
0.08mm2 (28AWG) to 4mm2 (11AWG) |
| Supervised circuits: |
Power, Input Zone 1 & Input Zone 2 |
| INPUTS | |
| Input: | Up to 2 zones (max 1km each); FT-68-EN, FT-68-EN-CAT, FT-68-EN-S, FT-78-EN, FT-78-EN-CAT, FT-78-EN-S, FT-88-EN, FT-88-EN-CAT, FT-88-EN-S |
| Zone length: |
1 to 1,000m (3,280ft) |
| End of line resistor: |
3.6kOhm (included) |
| Short circuit current: |
0.5mA |
| Max. zone voltage: | 5V |
| OUTPUTS | |
| Communications: | Two wire RS-485 Modbus RTU |
| Sounder: | 2.4kHz 92dBa @ 10cm Buzzer |
| Alarm: | 2x Form C volt-free relay contacts (resistive, common) Max V 30Vac or 42.4Vdc Max Current 2A Max Switching Power 60W, 62.5VA |
| Fault: | 2x Optoisolated phototransistor output (resistive, common) Max V 35Vdc Max Current 80mA Max Power Dissipation 150mW |