Signaline HD+ S Programmable Linear Heat Detection Cable with Stainless Steel Braid (50m) (SL-HDP-LHC-S)
SKU
SL-HDP-LHC-S
£543.74
£453.12
Signaline HD+ S Programmable Linear Heat Detection Cable with Stainless Steel Braid (50m) (SL-HDP-LHC-S)
Available on Backorder
This item is not currently in stock, but it is available to backorder. Contact us for lead time.
Product Details for Signaline HD+ S Programmable Linear Heat Detection Cable with Stainless Steel Braid (50m) (SL-HDP-LHC-S)
Signaline HD+ S is an advanced Programmable Temperature Linear Heat Detector with Stainless Steel Braid for increased mechanical protection. When used with the Signaline HD+ Controller and EOL, the user can select various alarm response temperature or class as well as pre-alarm settings.
The controller is easily adjusted for the length of cable being used.
Signaline HD+ S Programmable Temperature Linear Heat Detectors are resettable after an over-heat event as long as the maximum ambient temperature has not been exceeded.
Note: Signaline HD+ S must be used in conjunction with Signaline HD+ controller and EOL.
Key Features of the SL-HDP-LHC-S |
|---|
|
> Alarm temperature predetermined by chosen setting on Signaline HD+ Controller
> Stainless steel braid for increased mechanical protection > Min. zone length 50m, Max. zone length 500m > EN54--22:2015+A1:2020 (Class A1I, A2I and BI), UL521 “Heat Detectors for Fire Protective Signalling Systems” |
| Brand | Signaline |
|---|---|
| Manufacturer Part No. | SL-HDP-LHC-S |
Write Your Own Review
FAQ’s for Signaline HD+ S Programmable Linear Heat Detection Cable with Stainless Steel Braid (50m) (SL-HDP-LHC-S)
No questions yet. Be the first to ask the question!
Product Specification for Signaline HD+ S Programmable Linear Heat Detection Cable with Stainless Steel Braid (50m) (SL-HDP-LHC-S)
| Model: | Signaline HD+ (SL-HDP-LHC-S) |
| Alarm class: | EN54-22:2015+A1:2020 (Class A1I, A2I and BI) UL521 “Heat Detectors for Fire Protective Signalling Systems” |
| Operating temperature: | -40°C to +125°C |
| Environmental group: | II |
| Max. zone length: | 500m / 1640ft (all alarm settings) |
| Min. zone length: | 50m / 164ft (Class A1l/A2l and 54°C alarm settings) 30m/100ft (all other alarm settings) |
| Conductor resistance: | White core resistance per mtr ; Approx 17Ω/m Red core resistance per mtr; Approx 3.3Ω/m Clear core resistance per mtr (each); Approx 0.1Ω/m |
| Min. bend radius: | 75mm (3 in) |
| Overall diameter: | 5.33mm |
| Weight: | 39.3g per km |
| Construction: | Overall insulated, 4-core twisted with 100% coverage foil-shield and shield dump wire |
| Colour: | Silver |
| Recommending fixing: | Signaline Q Clip (stainless steel fixing required for EN54 compliance) |
| Note: Signaline HD+R must be used in conjunction with Signaline HD+ controller and EOL | |