The C-TEC EP210F Flush Mount Remote Status Unit (RSU) connects to the EP203 Automatic Extinguisher panel and provides remote system status indication, an LCD status display unit, manual release of extinguishant, an extinguishant mode keyswitch and three monitored inputs.

Key Features of the EP210F

> Designed to connect to the RS485 terminals on an EP203 Automatic Extinguisher Panel to provide remote system status indication via a 128 x 64 pixel LCD status display.
> Also includes a pull-down manual release button, a mode (auto/manual) keyswitch and a wide range of system status indicators.
> Three monitored input connections (Hold, Abort and Mode).
> Max. 8 remote status units per EP203 panel.
> Surface remote status units (EP210S) and weather proof enclosures (BF359/1) also available.

More information about C-TEC EP Extinguisher Release Remote Status Unit, Flush Mount (EP210F)

More Information
Brand C-TEC
Manufacturer Part No. EP210F
Primary Power Source 24V DC
System Type Conventional
Warranty 1 Year
Write Your Own Review
You're reviewing:C-TEC EP Extinguisher Release Remote Status Unit, Flush Mount (EP210F)
Your Rating

Datasheets and Manuals for C-TEC EP Extinguisher Release Remote Status Unit, Flush Mount (EP210F)

FAQ’s for C-TEC EP Extinguisher Release Remote Status Unit, Flush Mount (EP210F)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for C-TEC EP Extinguisher Release Remote Status Unit, Flush Mount (EP210F)

Power requirements 21-28VDC (200mA electronic fuse).
Quiescent current 7mA.
Auxiliary inputs Three: (1) Hold; (2) Abort; (3) Mode. A 6k8 EOL resistor must be fitted across the terminals of the last device on each monitored input circuit. Unused circuits must have the 6k8 resistor fitted a
Indicators Gen. fire; Fire Zones (x3); Gen. disablement; Hold; 1st Stage Output; 2nd Stage Output; Release Imminent (x2); Exting. Released; Abort; Gen. Fault; Man. Only; Man/Auto.
Controls Extinguishant release (housed in yellow casing); Operation keyswitch (Manual only or Manual & Auto).
Product dimensions (mm) 175 W x 250 H x 70 D mm. Hole required for flush mounting 156 W x 232 H x 51 D mm.
Construction & finish Metal.
IP Rating IP30.
Weight 1.338kg..
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.
Network specification RS485; Max. 8 remote status units (any mix) per EP203; Four wire connection (2 power, 2 data); Daisy-chain wiring.