Global Fire OCTO+ Fire Alarm Control Panel, 4 Loops (OCTO-4)

Global Fire OCTO-4 Loop Addressable Fire Alarm Control Panel

The OCTO+ is a versatile compact addressable Fire Alarm Control Panel which can be surface or recessed mounted. The powerful cause-and-effect programming capabilities along with enhanced system diagnostics performance make this control panel suitable for a wide range of applications from small to large buildings or sites with complex multiple areas.

With the addition of a network card, the NODE+ incorporates the advanced peer-to-peer, multi-master Chameleon Networking communications protocol. The Chameleon Network can accommodate up to 32 networked fire control alarm panels (NODEs). Each control panel (NODE) has its own internal configuration along with the entire Network configuration backed up, which provides a high level of networking security and resilience required for distributed fire detection and alarm systems.

The OCTO+fire alarm control panel uses either RS422 or Fibre Optic communications for the network, which is usually wired in a fault-tolerant loop configuration, providing multi-path system integrity for high-speed monitoring and data communication. Additional ethernet interfaces provide further networking options allowing the system to communicate over other infrastructures. The control panel also has the provision to connect to CHAMELEON repeater control panels, using any of the networking interfaces on the CHAMELEON Networking protocol.

The high contrast backlit blue LCD display provides a clear and effective user interface which can accommodate any type of custom characters or graphical symbols, allowing multiple language support as well as pictorial and customisable elements.

The OCTO+ can be securely accessed remotely via our proprietary ODYSSEY Graphics Interface. Integration with third-party Building Management Systems (BMS) is provided via a dedicated Modbus output.

The system programming can easily be programmed on-site via the onboard navigation keypad or by using the powerful PC CHAMELEON CONNECTOR configuration software which is downloaded to the control panel or broadcasted to the network via USB connection.


Key Features
> 4 addressable loops
> Network compatibility with the G-One, GEKKO and NODE+ control panels
> Connect to repeater panels via RS422, Fibre-Optic or TCP/IP
> 250 devices per loop (125 address limit)
> Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
> 32 individually programmable sounder addresses
> Full Self-Addressing Device support
> 2 Fire output relays (change-over) and 1 Fault relay (NC )
> 2 conventional alarm outputs (individually programmable)
> Loops monitored for high integrity
> 384 programmable zones
> 512 programmable sounder groups; 512 I/O groups
> 10,000 events log
> Available with ZEOS digital protocol
> Compatible with Global Fire ancillary modules
> Backlit LCD graphic display (240x64 px)
> Programme via integrated keypad or Loader PC software
> Multiple language support
> Integrated 16 LED fire zone indications
> Installer-friendly Auto-learn facility
> EN54-13, EN54-2, EN54-4 1328-CPR-0737 certified
More Information
ManufacturerGlobal Fire Equipment
MPNOCTO-4
Primary Power SourceMains Powered (230V)
System TypeAddressable
Number of Loops4
Number of Zones384
Protocol CompatibilityGFE ZEOS
ColourWhite
Warranty10 Years
Write Your Own Review
You're reviewing:Global Fire OCTO+ 4 Loop Fire Control Panel
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Product Code:OCTO-4
Product description:OCTO+ Fire Alarm Control Panel, 4 loop
Dimensions:W:345mm x H:375mm x D:139mm
Enclosure:White (RAL 9003), Red (RAL3001) or Anthracite (RAL 7016)
Mains power supply rating:
90V - 253V @ 50 Hz 65 W
Primary DC supply:
28.5V DC @ 2.4A (max)
Secondary supply:
21.6 (min.) - 27.2V (max) - Battery charger 27.5V DC
Primary addressable detection & alarm circuit:28.5V DC
Sounders conventional output circuit:28V DC
Battery Max. Capacity: (Internal)
2 x 12V 12Ah
Quiescent current:
(no devices)
64mA
Aux Power Output:
2 x 24V DC 300mA / 1 x 24V switched output
Max. Loop output current:
1-4 loop max 165 mA per loop quiescent / max 900mA per loop peak
Loop topology:
Class A or Class B
Loop/sounder cable:
Firetuf 2 x 1.5mm (max 1200m) or
2 x 2.5mm (max 2000m)
Conventional sounder circuits:
500mA for conventional sounder circuits a+b
Aux. Relays Fire:
2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
Aux. Relay Fault:
1 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
Graphical LCD display:
High definition, high contrast blue backlit 240 x 64 pixels
Communication channels:
3 x configurable communication ports
BMS output:
ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
Software connection:
USB type B
Event log:10,000 events
Operating/storage temp:
-10oC to +50oC
Humidity:Max 85% RH Non-condensing
Ingress protection/material:
IP30 / ABS
Weight:10.5 kg (inc battery)