SKU
EVC-P
£15.84
£13.20
Nittan EVC-P Evolution Conventional Photoelectric Optical Smoke Detector
In Stock
Product Details for Nittan Evolution Conventional Optical Smoke Detector (EVC-P)
Using a simple but effective technique, the EVC-P Optical Detector incorporates a chamber housing an Infra Red (IR) LED light and a photodiode light detector set at an obtuse angle preventing it from seeing the light.
When smoke enters the chamber the light bounces off the smoke particles and strikes the photodiode, causing it to generate an alarm condition when a set threshold value is met. The EVC-P Optical Detector is therefore more sensitive to larger smoke particles which tend to be caused by smoldering fires rather than fast flaming fires.
Please Note: Base Sold Separately
Key Features of the EVC-P |
|---|
|
> Optical Smoke Detection
> Omniview 360° LED > Internal Alarm Current Limiting Resistor > Wide Operational Voltage Range (12v-32v) > Approved to EN54-7:2000 + A1:2002 |
| Brand | Nittan |
|---|---|
| Manufacturer Part No. | EVC-P |
Write Your Own Review
FAQ’s for Nittan Evolution Conventional Optical Smoke Detector (EVC-P)
No questions yet. Be the first to ask the question!
Product Specification for Nittan Evolution Conventional Optical Smoke Detector (EVC-P)
| Manufacturer: | Nittan |
| Product Code: | EVC-P |
| Sensor Method: | Light Scatter |
| Sensor Element: | 1 x Light Emitting Diode |
| Operating Voltage: | 12V d.c to 32V d.c |
| System Voltage: | 24V d.c |
| Quiescent Current: | 50µA |
| Alarm Current: | 50mA |
| Current for external remote LED indicator: | 2mA |
| Operating Temperature: | – 10°C to + 55°C |
| Storage Temperature: | – 20°C to + 60°C |
| Charging Time: | 20 Seconds |
| Relative Humidity: | ≤ RH95% non-condensing |
| I.P. Protection Rating: | IP40 |
| Material: | ABS |
| Dimensions: | ∅104mm x 33mm (Sensor head) - ∅104mm x 48mm (Sensor head and UB-4) |
| Mass: | 118g (Sensor head) - 183g (Sensor head and UB-4 base) |
| EMC Conformance: | EN54-7:2000 |
| CE Conformity: | Yes |
| Standards / Ceritification: | EN54-7:2000 |