SKU
NC-DPO-W
£19.07
£15.89
Kidde Conventional Optical Smoke Detector (White) (NC-DPO-W)
Available to Order
This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.
Product Details for Kidde Conventional Optical Smoke Detector (White) (NC-DPO-W)
The Kidde NC-DPO-W is a conventional photoelectric (optical) smoke detector suitable for use in hotels, restaurants, office buildings, schools, banks, warehouses, libraries, computer rooms, switch rooms, etc.
Key Features of the NC-DPO-W |
|---|
|
> Supports drift compensation to enable good environmental adaptability
> Self-diagnostic > Local test activation with reed switch > Chamber contamination checking > All round LED visibility (360° viewing angle) avoids time spent on specific detector orientation > Configurable polling LED support > Remote indicator output > Removable sensing chamber for for easy maintenance > 2 Programmable smoke sensitivity levels |
| Brand | Kidde Commercial |
|---|---|
| Manufacturer Part No. | NC-DPO-W |
| Primary Power Source | 24V DC |
| System Type | Conventional |
| Sensor Type | Optical |
| Detectable Medium | Smoke |
| Colour | White |
| Warranty | 2 Years |
Write Your Own Review
FAQ’s for Kidde Conventional Optical Smoke Detector (White) (NC-DPO-W)
No questions yet. Be the first to ask the question!
Product Specification for Kidde Conventional Optical Smoke Detector (White) (NC-DPO-W)
| Code: | NC-DPO-W |
| Description: | Kidde Conventional Point Detector - Optical (White) |
| Dimensions: | 54.5 mm (including base) x 100 mm Ø |
| Status indication: | Red LED |
| User interface: | Via LED - polling, fault, contamination and alarm |
| Compatibility: | NC-Series conventional panels and Excellence series conventional zone monitors |
| Reset voltage: | <1 VDC |
| Reset time: | <10s |
| Alarm levels: | 2 |
| Connectivity: | Zone connection - 2 core (polarity sensitive), RI connection - 2-core (polarity sensitive) |
| Operating voltage: | 9.5 to 28 VDC (24 VDC typical) |
| Current consumption: | <60 μA (Quiescent) ≤55 mA (Alarm) |
| Cable specification: | >1.0 mm² |
| No. of cable cores: | 2 |
| Terminals: | 4 |
| Detection principle: | Optical, tyndall effect |
| Detection sensitivity: | Programmable |
| Detection zone length: | Panel dependent |
| Output quantity: | 1 |
| Output type / rating: | Remote indicator |
| Remote alarm output: | Supported |
| Colour: | White (RAL 9016) |
| Mounting: | Ceiling mount |
| Material (body): | ABS |
| Vandal proof: | No |
| Operating temperature: | -10 to +50°C |
| Application temperature: | -10 to +50°C (Class A1/A2) max. |
| Application temperature: | -10 to +65°C (Class B) max. |
| Relative humidity: | 0 to 95% noncondensing |
| IP rating: | IP2x |
| Compliancy/certification/standards: | CE, REACH, RoHS3, WEEE / CPR / EN54-7 |
| Compatible products: | Detection devices: NC-DB-W, NC-DB2R-W, NC-DBD-W, NC-DBR-W Notification device: PA25/3L |
| Weight: | ~110g (net) |