Product Details for Kidde Alarmline EN 54-22 Analogue LHD Composite Control Unit
Kidde AlarmLine II Analogue EN Controller (AAECU) and AlarmLine II Analogue EN end of line unit (AAECU-EOL). The controller monitors an AlarmLine II Analogue EN LHD sensor cable, configuration of alarm and pre-alarm temperatures as well as enabling simple interface to a main fire alarm or BMS system. It provides LED indications as well as an LCD. Internal push buttons allow for easy configuration without the need for a PC. Configuration via PC is also supported via a USB connection and optional configuration software AAECU-PCC.
Each control unit may have up to 500m of LHD sensor cable connected to it, acting as a single detection zone.The AAECU is supplied with an End-Of-Line unit (AAECU-EOL). The End-Of-Line unit is also available separately as a spare part.A junction box (AAECU-JUN) is also available separately should two pieces of cable need to be joined.
Key Features of the AAECU |
|---|
|
> VdS EN54-22:2015/prA1:2007
> Up to 500m of sensor cable per zone > Separate pre-alarm and alarm signals > Easy programmable interface > Enclosure temperature alarm > IP65 rated enclosure |
| Brand | Kidde Alarmline |
|---|---|
| Manufacturer Part No. | AAECU |
FAQ’s for Kidde Alarmline EN 54-22 Analogue LHD Composite Control Unit
Product Specification for Kidde Alarmline EN 54-22 Analogue LHD Composite Control Unit
| Code: | AAECU |
| Description: | Kidde AlarmLine II Analogue EN Control Unit |
| Dimensions: | Controller : W:182mm x H:180mm x D:90mm EOL unit : W:100mm x H:60mm x D:35mm |
| Electrical: | Operating voltage: 20 to 30 VDC Power consumption: 2W max. Power supply type: External Current consumption: 59 mA at 30 VDC |
| General: | Status indication: 4 x LED's (power, fault, pre-alarm & alarm) User interface: LCD display with internal configuration buttons Reset voltage: 5-28 VDC for minimum 3 seconds |
| Detection: | Principle: Heat - Classes A1I/A2I & BI Alarm temperature: +54°C (min.), +100°C (max.) |
| Input: | Quantity: 1 for remote reset Type / rating: 5-28 VDC (at 2 mA) for minimum 3 seconds |
| Output: | Quantity: 3 for fault, pre-alarm and alarm Type / rating: Pre-alarm and alarm : relay with NO/NC/C connections (2 A at 30 VDC), Fault : NC opto-isolated phototransistor output |
| Colour: | Light grey |
| Mounting type: | Surface, Wall |
| Material: | Polycarbonate |
| Environment: | Controller : -20 to +50°C EOL unit : -40 to +125°C IP Rating: Controller : IP65 (IK08) EOL unit : IP65 |
| Regulatory: | CE, EN54-22, VdS certified |
| Weight (net): | Controller 860 g EOL unit : 115 g |