The Kidde Alarmline AACUSP is a self programmable, Analogue Liner Heat Detection (LHD) cable control unit. It provides monitoring for any of the Alarmline II range of LHD sensor cables, configuration of alarm and pre-alarm temperatures as well as enabling a simple interface to a main fire alarm or BMS system.

The AACULP provides LED indications as well as an LCD. Internal pushbuttons allow configuration without the need for a PC. Each control unit may have up to 500m (1640ft) of LHD sensor cable connected to it, acting as a single detection zone. When the LHD sensor cable and the control unit are installed in different areas, a suitable interposing cable can be used to make the electrical connection between them.


Key Features of the AACUSP

> Self programmable
> UL521 and CE approval, UL/ULC listed
> Up to 500m of sensor cable per zone
> Separate pre-alarm and alarm signals
> Easy programmable interface
> Enclosure temperature alarm
> IP66 rated enclosure
> No nomograms or charts required

More information about Kidde Alarmline Analogue LHD Control Unit - Self Programmable

More Information
Brand Kidde Alarmline
Manufacturer Part No. AACUSP
Write Your Own Review
You're reviewing:Kidde Alarmline Analogue LHD Control Unit - Self Programmable
Your Rating

Datasheets and Manuals for Kidde Alarmline Analogue LHD Control Unit - Self Programmable

FAQ’s for Kidde Alarmline Analogue LHD Control Unit - Self Programmable

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Kidde Alarmline Analogue LHD Control Unit - Self Programmable

Code: AACUSP
Description: Kidde Alarmline II Analogue LHD Control Unit, self programmable
Dimensions: W:182mm x H:180mm x D:90mm
Operating voltage:
20 - 28 VDC
Current consumption: Quiescent: < 70 mA
Fault: < 70 mA
Pre-Alarm: < 80 mA
Alarm: < 80mA
Pre-alarm & alarm: < 100 mA
Detection: Ambient temp. up to 30°C: Alarm temp. 54°C
Ambient temp. up to 47°C: Alarm temp. 64°C / 72°C / 79°C
Ambient temp. up to 69°C: Alarm temp. 86°C / 100°C
Outputs: Pre-Alarm (Form C relay resistive load): 2A @ 30VDC / 0.25A @ 250VAC (62.5VA)
Alarm (Form C relay resistive load): 2A @ 30VDC / 0.25A @ 250VAC (62.5VA)
Fault (Opto-isolated phototransistor output) Max.: 50V @ 20mA
Inputs: Remote reset (isolated) 5s pulse: 20-28VDC
Zone length: 30.5m to 500m (100ft to 1640ft)
Material (body): Polycarbonate
Mounting type:
Recessed mount
Colour: Light grey
Environment: Operating temperature: -0°C to +50°C
IP66/IK08, Indoor, Outdoor
Relative humidity: 0 to 95% max. noncondensing
75% for <75 m cable & 54°C alarm setting
Regulatory: CE, UL certified
Weight: 815g (net)