Essential Cookies
This website only uses essential cookies for the functionality of our cart and checkout process. Read our cookie policy
The FP2864C is a versatile addressable fire panel supplied with 2 class-A loops. In addition to a generous backlit LCD display, it provides LEDs for indicating both fire and fault conditions with text descriptions for 16 fire zones on the front panel user interface. The panel may be upgraded with an additional 6 class-A loops as well as 48 zone indicators, full inter-panel networking facilities on both copper or fibre, as well as with a LON network bus that supports the Aritech LON700 devices and repeaters, amongst others.
The FP2864C provides extensive maintenance features, boasts powerful I/O programming and supports both Aritech 2000 and 900 series protocols.
Maintenance warnings are available whenever detectors reach contamination levels. Together with real time diagnostics and statistics per sensor, the FP2864C offers a wealth of in-depth information locally or by remote connections.
The FP2864C offers multiple auto-configuration options with extensive auto detection facilities facilitating quick initial setup even for large systems. Multiple repeaters in various formats may be connected over a 2-wire network with both class-A and B operating modes, whilst up to 31 fire panels may be networked together for large applications.
In addition to the comprehensive information LEDs, the panel's large LCD display allows for every device in the system to be described with up to 80 characters of descriptive text, as well as 40 characters for zone descriptions. Complete statistics and graphics indications for every device are available.
Several mechanisms for preventing false alarms, including floating background with automatic compensation, double knock and coincidence mode within and between zones, as well as soak test facilities allow the user complete piece of mind.
Up to 32 LON700 nodes are supported on the optional LON700 network. This includes LCD and LED repeaters, synoptic chart drivers, supervised in- and output boards, relay and open collector output boards, zone monitors and power supplies.
Key Features of the FP2864C-99 |
|---|
| > Configuration, maintenance and graphic PC software support > Up to 128 device addresses per loop > Full inter-panel network options > Full range of repeaters and LON700 devices > Networkable "black box" panels > Power supply for 72-hour autonomy > Default start-up and service modes > Programmable service reminders, on-line diagnostics and statistics > Maintenance warnings and soak testing facilities > One-man maintenance > Floating background and drift compensation > Programmable day/night functionality > Coincidence within and between zones > Timed and manual zone control > I/O programming with Boolean functions (maximum allocated input memory = 300) > EN54 and CPD certified |
| Brand | Aritech |
|---|---|
| Manufacturer Part No. | FP2864C-99 |
| Primary Power Source | Mains Powered (230V) |
| System Type | Addressable |
| Number of Loops (Fitted) | 2 |
| Max No. of Loops Possible | 8 |
| Number of Zones | 64 |
| Protocol Compatibility | Aritech 2000 Series |
| Colour | White |
| Warranty | 2 Years |
| Product no.: | FP2864C-99 |
| Description: | Kidde 2000 Series - Addressable Fire Panel with 2 to 8 loops 16 - 64 zones |
| Dimensions: | W:445mm x H:810mm x D:120mm Form factor: Large |
| Max. system capacity: | up to 30K (device count) |
| Network size: | more than 128 nodes |
| Power consumption: | 200VA |
| Operating voltage: | 230 VAC (+10%,a -15%), 47-63 Hz 21 to 28 VDC |
| Current consumption: | 200 mA @ 24 VDC (operation) <240 mA @ 24 VDC (alarm) |
| Loop capacity: | 8 max. |
| Cable rating: | <2 km, Ø 1 mm, 300 nF/km, 100 ohm |
| Zone capacity: | up to 256 max. |
| Standby battery: | Charger: 27.3 VDC at 20°C, 36 mV/°C Housing: 2 x 12 V (7 to 45 Ah) |
| Power supply: | Aux. 24VDC - 19 to 28 VDC @ 1 A (max) Aux. 5VDC - 5 VDC (±0.1V) 75 mA (max) |
| Loop specifications: | Loops per panel: 8 (Class A)/8 (Class B) Loop current: <500mA Addresses per loop: <128 (protocol dependent) |
| Inputs/Outputs: | Relays: 4 (2A @ 24 VDC - 60 W) Supervised relays: 4 (24 VDC, 30 ohm, 120 nF, 500 m) Inputs (Opto Isolated): 4 (15 VAC/0 to 28 VDC) Inputs (Supervision selectable): 4 Zone indicators per panel: 64 (fire & fault) |
| Colour: | Traffic white (RAL9016) |
| Mounting: | Surface |
| Operating temperature: | -5 to +40°C |
| Storage temperature: | -20 to +60°C |
| IP rating: | IP54 |
| Regulatory: | EN54-2, EN54-4 |
| Weight (net): | 15kg (no batteries) |