Kentec Sigma XT Extinguishant Control Panel (K11031M2)

SKU
K11031M2
£527.87 £439.89
Kentec Sigma XT Extinguishant Control Panel (K11031M2)

The Kentec Sigma XT Extinguishant Control Panel (K11031M2) is suitable for small to medium fixed firefighting installations. This single area panel has 3 detection zones and the extinguishant release can be configured to activate from any combination of detection zone inputs.

Sigma XT panels are both robust and easy to install having all the electronics mounted on a single, easily removable, steel plate.


Key Features
> Single or any combination of zones can be configured to release
> Configurable first stage sounder delays
> Configurable detection delays
> Zero time delay upon manual release option
> Compatible with I.S. barriers
> Non-latching zone input option to receive signals from other systems e.g. aspirating equipment
> Countdown timer shows time remaining until release
> Supports up to 7 x 4-wire status indicators
> Configurable extinguishant delays up to 60 seconds in 5 second steps
> Configurable extinguishant duration up to 5 minutes in 5 second steps
> Built-in extract fan control
> EN12094-1, EN54-2 and EN54-4 Approved
More Information
ManufacturerKentec Electronics
MPNK11031M2
Write Your Own Review
You're reviewing:Kentec Sigma XT Extinguishant Control Panel (K11031M2)
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Product Code:K11031M2
Product Dimensions:W:385mm x H:310mm x D:90mm
Surface mounting panel
Construction: 1.2mm mild sheet steel surface mount enclosure
IP Rating:IP30
Finish:Epoxy powder coated
Colour:lid & box BS 00 A 05 grey - fine texture
control plates & labels RAL 7047 light grey - satin
Weight:
6kg
Mains supply:230V AC +10%/-15% (100W max)
Mains supply fuse:1.6Amp (F1.6A L250V)
Power supply rating:3 Amps total including battery charge 28V +/- 2V
Maximum ripple current:200 millivolts
Battery type (Yuasa NP):2 x 12V sealed lead acid in series
Battery charge voltage:27.6V DC nominal (temperature  compensated)
Battery charge current:
0.7A maximum
Battery fuse:
20mm, 3.15A glass
Maximum current draw from batteries:
3 Amps
Quiscent current of panel in mains fail:0.095A
ROV output:Fused at 500mA with electronic fuse
Sounder outputs24V Fused at 500mA with electronic fuse
Fault relay contact rating:
30V DC 1A maximum
Fire relay contact rating:
30V DC 1A maximum
Local fire relay contact rating:30V DC 1A maximum
First stage contact rating:30V DC 1A maximum
Second stage contact rating:30V DC 1A maximum
Extract contact rating:30VDC 1A maximum
Zone quiescent current:2mA maximum
Terminal capacity:0.5mm2 -2.5mm2 solid or stranded wire
No. of detectors per zone:Dependent on type (max. 32)
No. of sounders per circuit:Dependent on type (max 0.5A per sounder circuit)
Detection circuit end of line:6K8 5% ½ W resistor
Monitored input end of line:6K8 5% ½ W resistor
Sounder circuit end of line:10K 5% ¼ W resistor
Extinguishant output end of line:1N4004 diode
No. of sounder circuits:2 x 1st stage, 1 x 2nd stage
No. of detection circuits:3
Extinguishant release output:Fused at 1 Amp
Extinguishant release delay:Adjustable 0 to 60 seconds (in 5 second steps)
Extinguishant release duration:Adjustable 60 to 300 seconds (in 5 second steps)
SIL, AL, FLT, RST inputs:Switched -ve, max resistance 100 Ohms
Detector alarm threshold:999 ohms to 400 ohms
Call point alarm threshold:399 ohms to 100 ohms
Short circuit threshold:99 ohms to 0 ohms
Head removal condition:15.5 to 17.5 volts
Cabling:FP200 or equivalent
Monitored inputs normal threshold:8K Ohm to 1K Ohm
Monitored inputs alarm threshold:999 ohms to 100 ohms
Monitored inputs short circuit threshold:99 ohms to 0 ohms
Status Indicator/Ancillary board connection:Two wire RS485 connection
Status unit power outputFused at 500mA with electronic fuse
Kentec Sigma XT Extinguishant Control Panel (K11031M2)