Kentec Sigma XT+ 4 Zone, 2 Area Extinguishing Control Panel (K21042M3)

SKU
K21042M3
£1,145.47 £954.56
Kentec Sigma XT+ 4-Zone, 2 Area Extinguishing Control Panel (K21042M3)

This Sigma XT+ Extinguishant Control Panel has 2 single area extinguishing control modules and an 8-Zone conventional detection module. The extinguishant areas have comprehensive sets of inputs and outputs and can be configured via a simple programming interface.

Surface Mount M3 enclosure W:385mm x H:520mm x D:110mm with space for 2 x 12V 12Ah SLA batteries.

With highly configurable extinguishing control modules, it provides an integrated control solution for extinguishing systems with up to four protected areas.

The fire detection section connects to the extinguishant control modules via a serial link which allows secure, bi-directional transfer of data between the two. Sigma XT+ modules may be mounted remotely in separate enclosures and connected to Sigma CP panels via this serial interface to provide central fire detection and control with distributed extinguishing systems.

Sigma XT+ modules may also be mounted separately from fire detection and control equipment and activated by addressable output modules or volt free contacts from other systems via two monitored activation inputs.


Key Features
> 4-Zone conventional detection module
> Extinguishant control modules for 2 areas
> Dual extinguishant outputs
> First & second stage sounder outputs
> First & second stage volt free changeover contacts
> Detection & Extinguishing controls and status indicators
> Released volt free contact
> Fault volt free contact
> Auto/Manual keyswitch
> Programmable extinguishant delays
> Programmable output duration
> Countdown indicator shows time until release in seconds
> Mode select and manual release controls
> Monitored remote manual release input
> Monitored remote Hold input
> Monitored remote Mode select (door interlock) input
> Monitored remote Released pressure switch input
> Monitored remote Low Pressure switch input
> Monitored Abort input
> Integral 3 Amp power supply 230V AC input
> Serial connection for Sigma Si status units and ancillary boards
> EN12094-1, EN54-2 and EN54-4 Approved
More Information
ManufacturerKentec Electronics
MPNK21042M3
Write Your Own Review
You're reviewing:Kentec Sigma XT+ 4 Zone, 2 Area Extinguishing Control Panel (K21042M3)
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Product Code:K21042M3
Product Dimensions:W:385mm x H:520mm x D:110mm
Construction: 1.2mm mild sheet steel surface mount enclosure
IP Rating:IP30
Finish:Epoxy powder coated
Colour:lid & box BS 00 A 05 grey - fine texture
control plates & labels RAL 7047 light grey - satin
Weight:
8kg (standard panel)
Mains supply:230V AC 50Hz+10-15% (100W max)
Mains supply fuse:1.6A (FL.6A L250V)
Power supply rating:3A inc battery charge 28V+/-2V
Maximum ripple current:200 millivolts
Battery charge voltage:27.6V DC nominal (temperature compensated)
Battery charge current:
0.7A maximum
Battery fuse:
20mm, 3.15A glass
Current draw in mains fail condition:
54 mA per module
Max. current draw from batteries:
3A
Sigma XT+ module Aux 24V output:
Fused at 500mA with electronic fuse - 1 per extinguishant area
Sigma CP Aux 24V output:
Fused at 2.5A - not available to user
1st & 2nd stage sounder outputs:21 to 28V DC Fused at 1A with electronic fuse
Fault relay contact rating:5 to 30VDC 1A maximum for each
Fire relay contact rating:
5 to 30V DC 1A maximum for each
Local fire relay contact rating:5 to 30V DC 1A maximum for each
First stage contact rating:5 to 30V DC 1A maximum for each
Second stage contact rating:5 to 30V DC 1A maximum for each
Extract contact rating:5 to 30VDC 1A maximum for each
Zone quiescent current:0mA minimum, 2mA maximum
Terminal capacity:0.5mm2 to 2.5mm2 solid or stranded wire
No. of detectors per zone:Dependent on type, typically 20
No. of sounders per circuit:Dependent on type and current consumption - typically 20+
Monitored input end of line:6K8 +/- 5% ½ W resistor
Sounder circuit end of line:10K +/- 5% ¼ W resistor
Extinguishant output end of line:1N4004 Diode
Extinguishant release output:21 to 28V DC. Fused at 1A
Extinguishant release delay:Adjustable 0 to 60 seconds (+/- 10%)
Extinguishant release duration:Adjustable 60 to 300 seconds
SIL, AL, FLT, RST inputs:Switched -ve, min resistance 0 Ohms, max resistance 100 Ohms
Zone normal threshold (allowable EOL):10K ohm to 2K ohm
Detector alarm threshold:1K ohms to 390 ohms
Call point alarm threshold:370 ohms to 150 ohms
Short circuit threshold:130 ohms to 0 ohms
Head removal condition:15.5 to 17.5 volts
Cabling:FP200 or equivalent (max capacitance 1uF max inductance 1mH)
Monitored inputs normal threshold (allowable EOL):10K ohm to 2K ohm
Monitored inputs alarm threshold:
2K ohms to 150 ohms +/- 5%
Monitored inputs short circuit threshold:
140 ohms to 0 ohms +/- 5%
Status unit/ancillary board connection:Two wire RS485 connection (EIA 485 specification)
Status unit power output:21 to 28V DC. Fused at 500mA with electronic fuse
Kentec Sigma XT+ 4 Zone, 2 Area Extinguishing Control Panel (K21042M3)