Hochiki FIRELINK-100 2 Pipe Aspirating Smoke Detector with Docking Station

SKU
FIRELINK-100
£1,696.75 £1,413.96
Hochiki FIRELINK-100 2 Pipe Aspirating Smoke Detector with Docking Station

The Hochiki FIRElink-100 is designed to provide very high-sensitivity smoke detection in a small package. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup; This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

The detector is designed to fit into a Docking Station which accepts all sampling pipes and cables leaving the detector to be fitted during the final commissioning phase.  This ensures that the detector is less likely to be damaged during installation.

Volt-free Fire 1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems.


Key Features
> Ultra small, low cost aspirating smoke detector for easy and discreet installation
> High sensitivity provided by laser based forward light scatter for reliable early warning
> Two sampling pipes up to 100 m (aggregate) in length (still air)
> False alarms reduced by unique laser sensing technology - able to discriminate against dust
> RS485 communications built in as standard for networking and remote communications
More Information
ManufacturerHochiki
MPNFIRELINK-100
Write Your Own Review
You're reviewing:Hochiki FIRELINK-100 2 Pipe Aspirating Smoke Detector with Docking Station
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Description Hochiki High Sensitivity Air Sampling Smoke Detector
Product Code FIRElink-100
Dimensions: W:300mm x H:220mm x D:85mm
Supply Voltage: 21.6 - 26.4 VDC
Current Consumption: 400 mA @ 24 VDC
Relay Contact Rating: 500 mA @ 30 V
Operating Temperature Range: 0 to +38 °C (UL268), -10 to + 60 °C (CEA4022)
Operating Humidity Range: 0 - 90% non-condensing
Measurement Range (obs/m):

0.03% to 25% Full Scale Deflection (FSD)
0.0015% to 25% Sensitivity Resolution
Detection Principle: Laser light scattering mass detection and particle evaluation
Particle Sensitivity Range: 0.003 μ to 10 μ
Dust Discrimination Principle: 3D3 Laser Dust Discrimination (LDD)
Maximum Sampling Pipe Length: 50m ( 2 x 25 m or 1 x 35 m) moving air (>1 ms) OR 100m (2 x 50 m OR 1 x 65 m) still air (max)
Sampling Pipe Diameter: ¾” nominal bore (27 mm O/D)
(EN54-20 performances)
Alarm Levels: 2 - “FIRE” and “FAULT” (2 additional levels available with optional Relay Card or APIC fitted)
IP rating: IP50
Sampling Pipe Inlets:
2
Exhaust Air Pipe Outlets:
1 (on optional Piped Exhaust docking station)
Weight: 3.8kg (with docking station)