This website uses cookies to ensure you get the best experience on our website. Read our cookie policy
SKU
CHQ-MRC2/FS(SCI)
£53.08 £44.23
Hochiki CHQ-MRC2/FS(SCI) Fail Safe Mains Relay Module with SCI
- Buy 10 for £52.26 £43.55 each and save 2%
- Buy 20 for £51.44 £42.87 each and save 3%
- Buy 50 for £50.62 £42.18 each and save 5%
The Hochiki CHQ-MRC2/FS(SCI) is a Single Input/Output Module, which provides a single, mains-rated relay output for the control of such devices as dampers, access control equipment (e.g. door magnets), extractors or plant and equipment shutdown. The monitored input can be used for local power supply fault monitoring or as a general-purpose input.
The unit is also available as a DIN Rail mountable version; with an integral short-circuit isolator. The CHQ-MRC2/FS(SCI) utilises simple DIL switches for reliable addressing.
Key Features |
---|
> Loop powered > Single loop address > Single mains rated relay contact > Relay Contact Rated at 250 VAC 5 A (resistive) & 48 VDC 2 A (resistive) > Auxiliary monitored input > Both models feature an integral short-circuit isolator > Fail safe relay control (check for control panel compatibility for fail safe operability) > DIN rail version available |
Manufacturer | Hochiki |
---|---|
MPN | CHQ-MRC2/FS(SCI) |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Description | Hochiki Fail Safe Analogue Mains Relay Controller |
Product Code | CHQ-MRC2/FS(SCI) |
Dimensions (mm): | L157 x H127 x H35 (Module plus Lid) H79 (CHQ-Module plus Lid plus CHQ,BACKBOX) |
Operating voltage: | 17 - 41 VDC |
Low power mode (typ): | 100 μA |
Quiescent current (typ): | 300 μA |
Current consumption: | 22 mA ± 20 % (polling) |
Current in short circuit: | 8 mA |
Maximum short circuit current: | 1 A |
Relay contact rating* **: | 48 VDC max, 2 A (resistive load), 250 VAC max, 5 A (resistive load) – For mains ac switching, the Control Panel must be compliant with Low Voltage Directive for SELV circuits |
Input EOL resistor: | 10 kΩ, ±5%, 0.25 W |
Input threshold level: | ON=470 Ω, Short cct <50 Ω, Open cct >100 KΩ |
Operating temperature range: | -10 °C to + 50 °C |
Storage temperature range: | -30°C to +60°C |
Max. humidity: | 95% RH non-condensing (at 40 °C) |
Colour, Case material: | CHQ Module & CHQ-BACKBOX White ABS, Module Lid Semi-Opaque Black ABS as standard (white version – CHQ-LID(WHT) also available) |
Weight: | 360 (add 235 to module weight when using CHQ-BACKBOX) |
* Fire alarm control panel compatibility required for these products. ** No fuses are fitted on this device. The relay output circuit must therefore be protected by a suitable over-current protection device to prevent excessive current through the relay contacts. Refer to the relay contact specification in the attached datasheet. |