Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

SKU
CHQ-ISM
£89.12 £74.27
Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module
Available to Order This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.

Product Details for Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

The Hochiki CHQ-ISM Sounder Control Module interfaces between the Hochiki Analogue system via a CHQ-DSC2(SCI) or conventional sounder outputs and the intrinsically safe sounder/beacon units via an intrinsically safe barrier. The module provides line monitoring for open or short circuits on the wiring connected to both the safe and hazardous areas.


Key Features of the CHQ-ISM

> Provides dual sounder circuits
> Provides fault-monitored input
> Interfaces between loop and I.S. sounders/beacons
> Fully monitored for short-circuits
> Requires 24 VDC external power supply
> Also available as a DIN module

More information about Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

More Information
Brand Hochiki
Manufacturer Part No. CHQ-ISM
Product Series Hochiki Intrinsically Safe
Primary Power Source 24V DC
System Type Addressable/Conventional
Protocol Compatibility Hochiki ESP
Warranty 3 Years
Write Your Own Review
You're reviewing:Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module
Your Rating

Datasheets and Manuals for Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

FAQ’s for Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Hochiki CHQ-ISM Intrinsically Safe Compatible Sounder Module

Description Hochiki Intrinsically Safe Sounder Interface Module
Product Code CHQ-IZM
PSU Supply voltage (typical):
24V
I.S. BARRIER 1 Voltage (max.): 28V
I.S. BARRIER 2 Voltage (max.): 28V
Quiescent current (max.): 50 mA
SNDR CCT 1 Current poweredwith 24V (typical):
12 mA
SNDR CCT 2 Current poweredwith 24V (typical): 12 mA
I.S. BARRIER 1 Load Current: 40 mA max.
I.S. BARRIER 2 Load Current: 40 mA max.
Maximum Cable Resistance on I.S. barrier terminals: 25R
EOL CCT 1: User Determined
EOL CCT 2: User Determined
Monitored input EOL: 10K Ω resistor (supplied)
Input Thresholds: Normal condition (10KΩ±5%): 10.5KΩ max.
On/Activated (>100KΩ): 100Ω min.
On/Activated (>50KΩ): 50Ω max.