Product Details for Hochiki CHQ-DZM(SCI)-IS Intrinsically Safe Compatible Dual Zone Monitor with SCI
The Hochiki CHQ-DZM(SCI)-IS is Dual Zone Module which is fully compatible with Hochiki's ESP analogue addressable protocol and I.S. equipment. It is supplied as an OEM version (as illustrated) which can be fitted within an IP67 rated enclosure. The unit is also available as a DIN Rail mountable module; both models feature an integral short-circuit isolator. Addressing is achieved via simple DIL switches.
The device is designed to allow up to 40 (20 per zone) Conventional I.S. CDX Range detectors (SLR-E-IS or DCD-1E-IS) in the hazardous area to be interfaced to Hochiki's ESP analogue addressable system within the safe area.
(Please note that this module should only be installed in the safe area).
The conventional zones on the CHQ-DZM(SCI)-IS do not support any line continuity options, therefore if Call Points are being interfaced they should be wired at the beginning of the zone.
An appropriate barrier must be used.
Key Features of the CHQ-DZM(SCI)-IS |
|---|
|
> Single loop address
> Requires an auxiliary 24 VDC supply > Supports two independent zones of Hochiki I.S. Conventional Detectors > Both zones fully monitored for short/open-circuit > DIN rail version available > Both models feature an integral short-circuit isolator |
| Brand | Hochiki |
|---|---|
| Manufacturer Part No. | CHQ-DZM(SCI)-IS |
| Product Series | Hochiki Intrinsically Safe |
| Primary Power Source | 24V DC |
| System Type | Addressable |
| Protocol Compatibility | Hochiki ESP |
| Warranty | 3 Years |
FAQ’s for Hochiki CHQ-DZM(SCI)-IS Intrinsically Safe Compatible Dual Zone Monitor with SCI
Product Specification for Hochiki CHQ-DZM(SCI)-IS Intrinsically Safe Compatible Dual Zone Monitor with SCI
| Description | Hochiki Analogue Dual Zone Monitor |
| Product Code | CHQ-DZM(SCI)-IS |
| Dimensions (mm): | (with lid ) L 157 x W 127 x D 35 |
| Operating voltage: | 17 - 41 VDC |
| Low power mode (typ): | 110 μA |
| Quiescent current (typ): | 330 μA |
| Current consumption (external): | (Quiescent) 2 mA, (Alarm) 70 mA (Both zones in fire) |
| Capacitance on zone: | 0.3 μF max. |
| Resistance on zone: | 50 Ω max. |
| Operating temperature range: | -10 °C to + 50 °C |
| Storage temperature range: | -30°C to +60°C |
| E.O.L. device options: | 10 KΩ resistor (supplied with unit) |
| Zone output voltage: | 15.3 - 17.1 V |
| Output rating*: | 24 VDC 8.5 mA |
| Colour, Case material: | Ivory White / ABS |
| Weight: | 682g |
| * Output Rating (24V 8.5mA) is for remote indication outputs | |