SKU
CHQ-DRC2(SCI)
£60.58
£50.48
Hochiki CHQ-DRC2(SCI) Dual Relay Controller with SCI
In Stock
Product Details for Hochiki CHQ-DRC2(SCI) Dual Relay Controller with SCI
The Hochiki CHQ-DRC2(SCI) is a Dual Relay Controller designed to provide two general-purpose relay outputs, each output can be driven separately for control of such devices as dampers or for control of plant and equipment shutdown. The monitored input can be used for local power supply fault monitoring or as a general-purpose input. The unit is also available as a DIN Rail mountable version both models feature an integral short-circuit isolator. The CHQ-DRC2(SCI) utilises simple DIL switches for reliable addressing. A back box is also available (CHQ-BACKBOX) which, when used in conjunction with the CHQ-DRC2(SCI), increases the IP rating to IP65.
Key Features of the CHQ-DRC2(SCI) |
|---|
|
> Loop powered
> Single loop address > 2 Independently controlled changeover relays > Relays contact rated at 30 V dc at 1 A > Auxiliary monitored input > DIN-Rail version available > Both models feature an integral short-circuit isolator > Both models approved by LPCB |
| Brand | Hochiki |
|---|---|
| Manufacturer Part No. | CHQ-DRC2(SCI) |
| Product Series | Hochiki ESP |
| Primary Power Source | 24V DC |
| System Type | Addressable |
| Protocol Compatibility | Hochiki ESP |
| Warranty | 3 Years |
Write Your Own Review
FAQ’s for Hochiki CHQ-DRC2(SCI) Dual Relay Controller with SCI
No questions yet. Be the first to ask the question!
Product Specification for Hochiki CHQ-DRC2(SCI) Dual Relay Controller with SCI
| Description | Hochiki Analogue Dual Relay Controller with SCI |
| Product Code | CHQ-DRC2(SCI) |
| Dimensions (mm): | L=157 x W=127 x D=35 (Module & Lid) D=79 (Module, Lid & CHQ-BACKBOX) (add 235 to module weight when using CHQ-BACKBOX) |
| Operating voltage: | 17 - 41 VDC |
| Low Power Mode (0.75s): | 170 μA |
| Quiescent current (typ): | 300 μA |
| Current consumption: | 22 mA ± 20 % (polling) |
| Current in short-circuit: | 8 mA |
| Maximum short-circuit current: | 1 A (loop) |
| Relay contact rating: | 30 VDC max, 1 A (resistive load) |
| Input E.O.L. resistor: | 10 kΩ, ±5%, 0.25 W |
| Input threshold level: | ON=470 Ω, Short cct <50 Ω, Open cct >100 KΩ |
| Operating temperature range: | -10 °C to + 50 °C |
| Storage temperature range: | -30°C to +60°C |
| Maximum humidity: | 95% RH - Non Condensing (at 40°C) |
| Colour and enclosure material: | CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS, Module Lid Semi- Opaque Black ABS as standard (white version – CHQ-LID(WHT) also available) |
| Weight: | 343g |