Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

SKU
CHQ-DIM2(SCI)
£48.92 £40.77
Hochiki CHQ-DIM2(SCI) Dual Input Module with Short Circuit Isolator
<span style="color: Chocolate;">Limited Stock</span> Limited Stock

Product Details for Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

The Hochiki CHQ-DIM2(SCI) is a Dual Input Module designed to interface to a variety of inputs such as door contacts, sprinkler flow/door switches and plant equipment.

Also available as a DIN Rail mountable version; both models feature an integral short-circuit isolator

A back box is also available (CHQ-BACKBOX) which, when used in conjunction with the CHQ-DIM2(SCI), increases the IP rating to IP65


Key Features of the CHQ-DIM2(SCI)

> Single Loop Address
> Loop Powered
> 2 Independent Inputs for Monitoring of Volt Free Contacts
> Each Input can be Configured to Monitor either Normally Open or Normally Closed contacts
> DIN-Rail version available
> Both models feature an integral SCI
> Both models approved by LPCB

More information about Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

More Information
Brand Hochiki
Manufacturer Part No. CHQ-DIM2(SCI)
Product Series Hochiki ESP
Primary Power Source 24V DC
System Type Addressable
Protocol Compatibility Hochiki ESP
Warranty 3 Years
Write Your Own Review
You're reviewing:Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI
Your Rating

Datasheets and Manuals for Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

FAQ’s for Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Hochiki CHQ-DIM2(SCI) Dual Input Module with SCI

Description Hochiki Analogue Dual Input Module with SCI
Product Code CHQ-DIM2(SCI)
Dimensions: L=157 x W=127 x D=35 (module inc lid)
D=79 (module inc lid plus CHQ-BACKBOX)
(add 235 to module weight when using
CHQ-BACKBOX)
Operating voltage: 17 - 41 VDC
Quiescent current (typ): 280 μA
Current consumption:
22 mA ± 20 % (polling), 4.3 mA (both inputs active)*1
Current in short-circuit: 8 mA
Maximum short-circuit current: 1 A
Input line resistance: ON threshold <50 Ω, OFF threshold >100 KΩ
Operating temperature range: -10 °C to + 50 °C
Storage temperature range: -30°C to +60°C
Maximum humidity: 95% RH - Non Condensing (at 40°C)
Colour and enclosure material: CHQ Module & CHQ-BACKBOX White ABS, Module Lid Semi-Opaque Black, ABS as standard (white version – CHQ-LID(WHT) also available)
Weight: 327g
Fire alarm control panel compatibility required for these products.
* 1 Note: - Add 85 μA per input for normally closed contact monitoring