The Hochiki CHQ-DIM2(SCI) is a Dual Input Module designed to interface to a variety of inputs such as door contacts, sprinkler flow/door switches and plant equipment.
Also available as a DIN Rail mountable version; both models feature an integral short-circuit isolator
A back box is also available (CHQ-BACKBOX) which, when used in conjunction with the CHQ-DIM2(SCI), increases the IP rating to IP65
Key Features |
---|
> Single Loop Address > Loop Powered > 2 Independent Inputs for Monitoring of Volt Free Contacts > Each Input can be Configured to Monitor either Normally Open or Normally Closed contacts > DIN-Rail version available > Both models feature an integral SCI > Both models approved by LPCB |
Manufacturer | Hochiki |
---|---|
MPN | CHQ-DIM2(SCI) |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Description | Hochiki Analogue Dual Input Module with SCI |
Product Code | CHQ-DIM2(SCI) |
Dimensions: | L=157 x W=127 x D=35 (module inc lid) D=79 (module inc lid plus CHQ-BACKBOX) (add 235 to module weight when using CHQ-BACKBOX) |
Operating voltage: | 17 - 41 VDC |
Quiescent current (typ): | 280 μA |
Current consumption: | 22 mA ± 20 % (polling), 4.3 mA (both inputs active)*1 |
Current in short-circuit: | 8 mA |
Maximum short-circuit current: | 1 A |
Input line resistance: | ON threshold <50 Ω, OFF threshold >100 KΩ |
Operating temperature range: | -10 °C to + 50 °C |
Storage temperature range: | -30°C to +60°C |
Maximum humidity: | 95% RH - Non Condensing (at 40°C) |
Colour and enclosure material: | CHQ Module & CHQ-BACKBOX White ABS, Module Lid Semi-Opaque Black, ABS as standard (white version – CHQ-LID(WHT) also available) |
Weight: | 327g |
Fire alarm control panel compatibility required for these products. * 1 Note: - Add 85 μA per input for normally closed contact monitoring |