Available to Order
This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.
Product Details for GST 1 Loop Addressable Fire Alarm Panel (GST200N-1)
GST200N Intelligent Fire Alarm Control Panels are designed to comply with EN54-2 and EN54-4 standards with the benefits of simple installation, operation, and easy maintenance. 1 loop addressable panel which is suitable for small buildings such as offices, restaurants, shops, etc.
Key Features of the GST200N-1 |
|---|
|
> Max. 30 zones, each zone has its own alarm and fault/disable indicator and a label
> Single loop panel capacity 235 addressable devices. Can be extended to 2 loops by using an additional loop card (LC200). > Compatible with GST intelligent and digital products > 8 lines x 18 characters LCD screen > 15 LEDs to display important information > Non-Volatile memory ensures no loss of data even if power supply is accidentally removed > Wide range power supply > Sounder strobe output provides 0.5 A / 24 V load, compatible with GST conventional sounders > RS232 interface enables communication with PC, advanced user friendly programming software including ‘Fuzzy logic' > RS485 (max 32 panels w/ card) or CAN (max 240 panels w/ card) interface enables networking, built-in RS485 repeater output (max. 10 repeaters) > Multiple language options (separate SKUs) > Optional panel printer and GMC graphic station > PAS and Acknowledge Function, Dirty Detector Reporting, Walk Test Function |
| Brand | GST |
|---|---|
| Manufacturer Part No. | GST200N-1 |
Write Your Own Review
FAQ’s for GST 1 Loop Addressable Fire Alarm Panel (GST200N-1)
No questions yet. Be the first to ask the question!
Product Specification for GST 1 Loop Addressable Fire Alarm Panel (GST200N-1)
| Electrical | |
|---|---|
| Power consumption | Standby: 21 Ah / 24 VDC |
| Operating voltage | 100 to 240 VAC, 50/60 Hz |
| Current consumption | 1.5 A |
| Loop | |
| Maximum loop capacity | 1 |
| Quantity of devices per loop | 235 |
| Cable rating | Min. 1.0 mm2, ideally 1.5 mm2, 1500 m |
| Zone | |
| Maximum zone capacity | up to 30 |
| Output | |
| Output quantity | 3 |
| Output type and rating | Min. 1.5 mm2, ideally 2.5 mm2 |
| Fire alarm signalling | 500 mA / 24 VDC / NO-NC-Active |
| Fault signalling | NO / NC |
| Termination | 4k7 ohm |
| Physical | |
| Form factor | Large |
| Physical dimensions | 580 x 420 x 202 mm (H x W x D) |
| Mounting type | Surface mount |
| Environmental | |
| Operating temperature | 0 to +40°C |
| Relative humidity | ≤95% noncondensing |
| IP rating | IP30 |
| Regulatory | |
| Certification | CE, LPCB |
| Standards | EN54-2 EN54-4 |