Product Details for FFE Fireray 3000 Anti-Condensation Heater (3000-204)
The Fireray ® 3000 Anti-Condensation Heater has been designed to be used in environmental conditions where condensation affects the operation of optical beam smoke detectors.
Condensation occurs when the surrounding air is at a higher temperature than the surface that it comes in contact with. As air contains water, in the form of vapour, this will deposit on the cooler surface thus forming condensation.
The design of the Fireray ® Anti-Condensation Heater utilises forced air which results in a circulating current of warm air maintaining the detector lens at an incrementally higher temperature than the surrounding air. The heater will reduce the likelihood of condensation forming on the lens which, in turn, reduces the potential for false alarms.
Key Features of the 3000-204 |
|---|
|
> Bespoke bracket to ensure optimum performance or heater
> Designed to prevent the build-up of condensation > For use in temperature-controlled storage areas and cold environments > Order heater separately for transmitter and receiver |
| Brand | Fire Fighting Enterprises |
|---|---|
| Manufacturer Part No. | 3000-204 |
FAQ’s for FFE Fireray 3000 Anti-Condensation Heater (3000-204)
Product Specification for FFE Fireray 3000 Anti-Condensation Heater (3000-204)
| Code: | 3000-204 |
| Description: | Fireray Anti-Condensation Heater |
| Operating voltage: | 24V AC/DC |
| Power Consumption @ 24V: | 20W |
| Max. in-rush current: | 3A |
| Steady-state current @ 24V: | 0.8A (typical) |
| Operating temperature: | -10 to +45ºC |
| Recommended fuse rating: | T2A |
| Connections: | 4 leads (2 for heater, 2 for fan) |
| Average temp. increase of lens above ambient: | 10°C |
| Weight: | 275g |