Product Details for Fike CIE-A-400 1-2 Loop Addressable Fire Alarm Panel c/w 1 Loop Card (540-0001)
The Fike CIE-A-400 Addressable Fire Alarm Control Panel (540-0001) is a powerful addressable fire panel fitted with 1 loop card as standard and is expandable to 2 loops with the addition of an extra loop card (540-0003).
The CIE-A-400 panel supports up to 200 devices per loop, covering a maximum loop length of 2KM. It offers two configurable Monitored Input Circuits, two configurable Monitored Output Circuits, two configurable Relays, and one Fault Relay. With the Peripheral Bus Circuit, you can connect up to 8 Repeater Panels for extended coverage.
The system allows for flexible configuration with 3 alarm stages and comprehensive 'Zone to Zone' Cause and Effect programming across all 32 panel zones. It includes Alarm Confirmation and Delay Timers, along with 32 additional output zones for more complex programming needs.
Compatible with Fike's addressable devices, the CIE-A-400 utilises soft addressing principles, eliminating the need for manual device addressing and preventing duplicate addressing issues. Operating parameters can be easily configured from the panel or OSP programming software and stored in device flash memory. This advanced digital protocol ensures faster and more reliable communication between detectors and the control panel.
Key Features of the 540-0001 |
|---|
|
> 1-2 loop addressable fire alarm panel (fitted with 1 loop card as standard)
> Expandable to 2 loops with an additional loop driver card (540-0003) > Compatible with Fike's ASD addressable range of devices > Faster and easier installation > Improved and easier to use OSP software > Simple, yet intuitive end user interface > Enhanced service and fault finding tools > Utilises soft addressing to eliminate physical address changes at each device > Faster, more reliable communication between panel and devices > Supports up to 200 Fike addressable devices per loop (including up to 100 sounders at 85 dB per loop) > Supports a maximum loaded loop length of 2km > Fire and fault event log > Provides configurable monitored input and output circuits, configurable relays and fault relay > Peripheral bus circuit to add repeater panels > LCD graphical user display |
| Brand | Fike |
|---|---|
| Manufacturer Part No. | 540-0001 |
| Product Series | CIE-A-200/CIE-A-400 |
| Primary Power Source | Mains Powered (230V) |
| System Type | Addressable |
| Number of Loops (Fitted) | 1 |
| Max No. of Loops Possible | 2 |
| Number of Zones | 32 |
| Protocol Compatibility | Fike SITA |
| Colour | White |
| Warranty | 2 Years |
FAQ’s for Fike CIE-A-400 1-2 Loop Addressable Fire Alarm Panel c/w 1 Loop Card (540-0001)
Product Specification for Fike CIE-A-400 1-2 Loop Addressable Fire Alarm Panel c/w 1 Loop Card (540-0001)
| Dimensions Panel (WxHxD): | 353mm x 333mm x 117mm |
| Operating Temperature: | +5°C to +40°C |
| IP Rating | IP30 |
| Mains Supply Input: | 230V AC Nominal |
| Standby Battery Requirement: | 2 x 7/9Ah 12V Sealed Lead Acid (2 x 17 Ah with extended battery box) |
| Max Number of Loops: | 2 |
| Max Loop Length: | 2000 Metres |
| Max Conductor Resistance: | 24 Ohms |
| Loop Loading: | 450 DLU (200 Devices Max)* |
| Loop Operating Voltage: | 40V DC |
| Standby: | 24V DC |
| Max Loop Current: | 500mA |
| Number of Supported Zones: | 32 |
| LCD Display: | LCD Graphical Display |
| Device Labels: | 31 Characters |
| Event Log: | 1000 Events |
| Repeater Panels: | 8 Max |
| Aux Power Output: | 30V DC 350mA |
| Inputs and Outputs: | Inputs: 2 x Monitored Inputs (3k3 EOL, 680R Firing Resistor) Outputs: 3 x Volt Free Relay (30V DC @ 1A Max) Monitored Outputs: 2 x (32V DC @ 250mA Max, 10k EOL). Each monitored output may be configured as a Conventional Sounder Circuit, a Fire Output or as a Common Fault Output. |