The C-TEC EP211 Economy Status Unit (ESU) connects to the EP203 Automatic Extinguisher Panel and provides remote indication of extinguishant “release imminent” with a mode select switch (Manual Only or Manual & Automatic).
Key Features of the EP211 |
|---|
|
> Designed to connect to the EP203 Automatic Extinguisher Panel to provide remote system status indication via three LEDs
> Includes a mode (auto/manual) keyswitch > Mounts on a standard UK single gang 25mm flush or surface back box > Max. 8 economy status units per EP203 panel |
| Brand | C-TEC |
|---|---|
| Manufacturer Part No. | EP211 |
| Primary Power Source | 24V DC |
| System Type | Conventional |
| Warranty | 1 Year |
Write Your Own Review
FAQ’s for C-TEC EP Extinguisher Release Economy Remote Status Unit, Single Gang (EP211)
No questions yet. Be the first to ask the question!
Product Specification for C-TEC EP Extinguisher Release Economy Remote Status Unit, Single Gang (EP211)
| Power requirements | 21-28VDC (100mA electronic fuse). |
| Quiescent current | 5mA. |
| Auxiliary inputs | None. |
| Indicators | Release Imminent; Manual/Automatic operation; Manual Only operation. |
| Controls | Operation keyswitch (Manual only or Manual & Auto). |
| Product dimensions (mm) | 87 W x 87 H x 35 D mm. Can be mounted on a standard UK 25mm single gang flush or surface back box. |
| Construction & finish | Plastic. |
| IP Rating | IP40. |
| Weight | 86g |
| Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
| Network specification | Max. 8 EP211's per EP203 panel. Four wire connection (2 power, 2 data); Daisy-chain wiring. A 6K8 end of line resistor must be connected across the terminals of the last EP211 in the chain. |