C-TEC CAST-PRO Addressable Heat Detector (CP402)

SKU
CP402
£37.37 £31.14
C-TEC CAST-PRO Addressable Heat Detector (CP402)
  • Buy 10 for £35.93 £29.94 each and save 4%
Available on Backorder This item is not currently in stock, but it is available to backorder. Contact us for lead time.

Product Details for C-TEC CAST-PRO Addressable Heat Detector (CP402)

The C-TEC CP402 is a CAST-PRO addressable heat detector certified to EN54-5 & 17. It is compatible with C-TEC's range of CAST protocol fire detection panels and field devices.


Key Features of the CP402

> A programmable CAST-PRO heat detector
> Certified to EN54-5 & 17
> Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels
> Onboard short circuit loop isolator
> Includes two 8mm x 2mm ultra-bright red LED indicating strips
> Three operation modes – can be programmed to operate as an A1R, A2 or B heat detector
> <1mA alarm current
> 570A typical quiescent current @ 40V DC
> Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag

More information about C-TEC CAST-PRO Addressable Heat Detector (CP402)

More Information
Brand C-TEC
Manufacturer Part No. CP402
Primary Power Source 24V DC
System Type Addressable
Protocol Compatibility C-TEC CAST
Sensor Type Thermistor
Detectable Medium Heat
Warranty 1 Year
Write Your Own Review
You're reviewing:C-TEC CAST-PRO Addressable Heat Detector (CP402)
Your Rating

Datasheets and Manuals for C-TEC CAST-PRO Addressable Heat Detector (CP402)

FAQ’s for C-TEC CAST-PRO Addressable Heat Detector (CP402)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for C-TEC CAST-PRO Addressable Heat Detector (CP402)

Approvals/certifications CPR number 0063-CPR-242190023, KIWA certified to EN54-5 & 17.
Compatibility Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels.
Type Class A1R, Class A2 or Class B Heat (Programmable).
Sensitivity 3 Detection Modes (class A1R, A2 or B heat, default is Class A2).
Supply wiring 2-wire, polarity sensitive.
Supply/operating voltage 22 to 40V DC.
Quiescent current 570uA @ 40V.
Alarm current (Imax at Vmin) <1mA.
Alarm current (Iavg at Vmin) <1mA.
Sound pressure level (LAFmax) at Vmax at 1m N/A.
VAD category & coverage N/A.
Indicators 2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
Connections Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm) 105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base).
IP Rating IP21C
Weight 118g (not in base); 172g (in base).
Operating conditions/temperature -10ºC to +50ºC. Max relative humidity: 95% (non-condensing)
Notes Requires a CA408 CAST base. CA408R relay base also available.