Product Details for C-TEC CAST Addressable Input Output Module (CA730)

The C-TEC CA730 is an addressable CAST input output module, compatible with C-TEC's range of CAST protocol fire detection panels and field devices.


Key Features of the CA730

> LPCB certified to EN54-17 & 18 and Kiwa Telefication certified to EN54-13.
> Incorporates the functions of a switch monitor, zone monitor and output unit.
> Can be configured to monitor any combination of:- • Up to 20 conventional detectors & 10 MCPs • Any normally open switch with an EOL resistor fitted. • A simple normally open or closed switch (non-fault monitored).
> Onboard short-circuit loop isolator.
> 5.5mA typical alarm current (1.3mA typical quiescent current) @ 22-40V DC.
> Indicators for Loop polling, input faults and relay status.
> Can switch 1A@30V DC (or 0.3A@125V AC)
> Includes volt free changeover contacts that can be used to trigger rollershutter doors, gas shut-off valves, smoke vents, etc.
> Mountable on a C-TEC NCP-26 surface box or a standard UK 25mm double gang back box (not supplied).

More information about C-TEC CAST Addressable Input Output Module (CA730)

More Information
Brand C-TEC
Manufacturer Part No. CA730
Primary Power Source 24V DC
System Type Addressable
Protocol Compatibility C-TEC CAST
Warranty 1 Year
Write Your Own Review
You're reviewing:C-TEC CAST Addressable Input Output Module (CA730)
Your Rating

Datasheets and Manuals for C-TEC CAST Addressable Input Output Module (CA730)

FAQ’s for C-TEC CAST Addressable Input Output Module (CA730)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for C-TEC CAST Addressable Input Output Module (CA730)

Approvals/certifications LPCB certified to EN54-17 & 18 and Kiwa Telefication certified to EN54-13.
Compatibility Compatible with C-TEC's XFP/ZFP CAST Addressable Fire Panels.
Application/operation Incorporates the functions of a switch monitor, zone monitor and output unit in one device.
Supply/operating voltage 22 to 40V DC.
Quiescent current 1.3mA typical.
Activation current 5.5mA @ 22 to 40V DC.
Auxiliary relays One volt-free single pole changeover relay rated at 1A @ 30V DC (or 0.3A @ 12 V AC). Non-monitored. Clean contact.
Auxiliary inputs One monitored input that can be set to operate as a single zone monitor to support up to 20 ActiV detectors and 10 MCPs or (2) a monitored normally-open switch, triggered by a 470R.
Indicators Active (Lit Red): relay activated; monitored zone triggered or monitored switch closed; Polling (Flashing Red): communication check with the panel; Input Fault (Lit Yellow): fault detected
Connections Six 45º screw-type connectors that can take 0.5-2.5mm2 cable: +Ve & -Ve Loop In; +Ve & -Ve Loop Out; Zone +Ve & -V. Also includes N/O, N/C & C relay connections.
Product dimensions (mm) 147 W x 87H x 22 D mm. Can be mounted on a standard 25mm UK flush or surface double gang back box.
Construction & finish ABS Polycarbonate plate with a 200 micron two-tone grey velvet polyester label with red and white detailing.
IP Rating IP40 when correctly installed.
Weight 122g.
Operating conditions/temperature -10ºC to +55ºC.