Product Details for C-TEC CAST Addressable Input Output Module (CA730)
The C-TEC CA730 is an addressable CAST input output module, compatible with C-TEC's range of CAST protocol fire detection panels and field devices.
Key Features of the CA730 |
|---|
|
> LPCB certified to EN54-17 & 18 and Kiwa Telefication certified to EN54-13.
> Incorporates the functions of a switch monitor, zone monitor and output unit. > Can be configured to monitor any combination of:- • Up to 20 conventional detectors & 10 MCPs • Any normally open switch with an EOL resistor fitted. • A simple normally open or closed switch (non-fault monitored). > Onboard short-circuit loop isolator. > 5.5mA typical alarm current (1.3mA typical quiescent current) @ 22-40V DC. > Indicators for Loop polling, input faults and relay status. > Can switch 1A@30V DC (or 0.3A@125V AC) > Includes volt free changeover contacts that can be used to trigger rollershutter doors, gas shut-off valves, smoke vents, etc. > Mountable on a C-TEC NCP-26 surface box or a standard UK 25mm double gang back box (not supplied). |
| Brand | C-TEC |
|---|---|
| Manufacturer Part No. | CA730 |
| Primary Power Source | 24V DC |
| System Type | Addressable |
| Protocol Compatibility | C-TEC CAST |
| Warranty | 1 Year |
Write Your Own Review
FAQ’s for C-TEC CAST Addressable Input Output Module (CA730)
No questions yet. Be the first to ask the question!
Product Specification for C-TEC CAST Addressable Input Output Module (CA730)
| Approvals/certifications | LPCB certified to EN54-17 & 18 and Kiwa Telefication certified to EN54-13. |
| Compatibility | Compatible with C-TEC's XFP/ZFP CAST Addressable Fire Panels. |
| Application/operation | Incorporates the functions of a switch monitor, zone monitor and output unit in one device. |
| Supply/operating voltage | 22 to 40V DC. |
| Quiescent current | 1.3mA typical. |
| Activation current | 5.5mA @ 22 to 40V DC. |
| Auxiliary relays | One volt-free single pole changeover relay rated at 1A @ 30V DC (or 0.3A @ 12 V AC). Non-monitored. Clean contact. |
| Auxiliary inputs | One monitored input that can be set to operate as a single zone monitor to support up to 20 ActiV detectors and 10 MCPs or (2) a monitored normally-open switch, triggered by a 470R. |
| Indicators | Active (Lit Red): relay activated; monitored zone triggered or monitored switch closed; Polling (Flashing Red): communication check with the panel; Input Fault (Lit Yellow): fault detected |
| Connections | Six 45º screw-type connectors that can take 0.5-2.5mm2 cable: +Ve & -Ve Loop In; +Ve & -Ve Loop Out; Zone +Ve & -V. Also includes N/O, N/C & C relay connections. |
| Product dimensions (mm) | 147 W x 87H x 22 D mm. Can be mounted on a standard 25mm UK flush or surface double gang back box. |
| Construction & finish | ABS Polycarbonate plate with a 200 micron two-tone grey velvet polyester label with red and white detailing. |
| IP Rating | IP40 when correctly installed. |
| Weight | 122g. |
| Operating conditions/temperature | -10ºC to +55ºC. |