The Input/Ouput expansion card is designed to provide additional relay outputs and/or inputs when interfacing to other systems. The Input/Ouput expansion card plugs into the APIC interface slot in each detector and cannot be used in conjunction with an APIC Card.
The Input/Ouput expansion card provides detector inputs that may be programmed for Remote Day/Night Mode Changeover, Remote Reset or ClassiFire Override as well as power
supply fault monitoring. ClassiFire Override is a particularly useful feature that enables the normal detector sensitivity to be reduced by a preprogrammed percentage to avoid unwanted alarms from a predictable event such as theatre stage effects or open fires in heritage buildings.
The Input/Ouput expansion card provides detector outputs for the 4 alarm levels, and the fault output. The fault output is normally closed, and open in case of a fault.
Key Features |
---|
> 5 Outputs (4 alarm levels + fault) > 3 Inputs (programmable) > Compatible with Micra 10, Micra 5 and Micra 100 > Compatible with Senator 10, 25 and 100 > Compatible with LaserSense 10, 25 and 100 |
Manufacturer | AirSense |
---|---|
MPN | 9-30436 |
Write Your Own Review
Sort By:
No questions yet. Be the first to ask the question!
Code: | 9-30436 |
Description: | AirSense Input/Output expansion card for Micra 10, Micra 25 and Micra 100, and variants |
Dimensions: | W:71mm x H:102mm x D:26mm |
Mechanical: | Size: 71mm (W) x 102mm (H) x 25,5mm (D) Mounting: 4 screws (supplied with unit) |
Outputs: | Relays: 4 (Pre-alarm, Alarm, Alarm2 & Aux Alarm) + 1(Fault) Rating: 1A @ 24V |
Operating temperature: | -10 to +60°C |
Relative humidity: | 0 to 90% non-condensing |
Environment: | Indoor |
Certification: | EN54-20, FM, UL |