AirSense Modulaser Command Module

SKU
9-30782
£1,729.74 £1,441.45
AirSense Modulaser Command Module

The AirSense ModuLaser is a scalable aspirating smoke detection solution. This Command display module communicates via an RS-485 interconnection with the added functionality to control various modules over SenseNET. It supports up to 127 modules across the SenseNET network and features a user interface consisting of a TFT colour display, navigation buttons and status LEDs. Configuration of the Command Display Module (and associated detectors across the SenseNET network) can be done via the user interface, or via a computer using Remote software. The TFT color display supports simple operations like changing configuration options via a menu driven structure, as well as advanced features such as viewing the chart recording in graphical format.

The 127 supported modules can be any combination of ModuLaser modules as well as Micras and HSSD2s. The use of the Command Display Module creates an easy-to-use central point from where all modules/detectors on the network can be accessed and all alarms / faults are reported. Ideal for use in hostile environments. Forward scattering optical detection adds early warning capability without the risk of nuisance alarms.  Environmental compensation technology adds to its reliability.


Key Features
> Modular Design : Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap.
> Zoned aspirating smoke detection: Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module.
> Simplified installation : Docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit.
> Intuitive user interface : Bright easy-to-see colour TFT display and universal navigation and control buttons.
> Easy pipe connection : The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal.
More Information
ManufacturerAirSense
MPN9-30782
Write Your Own Review
You're reviewing:AirSense Modulaser Command Module
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Code: 9-30782
Description: AirSense ModuLaser, Command display module
Dimensions: W:110.5mm x H:133.5mm x D:300mm
Status indication: LEDs
User interface: TFT and navigation buttons on Normal and Command Display Modules
Alarm levels: 4 (Aux,​ Pre-alarm,​ Alarm and Alarm 2)
Event log: 20,000 events per module
RS485 support: Yes (SenseNET and SenseNET+)
Connectivity: USB (x2),​ IP and APIC on Display Module,​ with Modbus on Command Display Module
Operating voltage: 18 - 30 VDC
Current consumption: Display Module (at 24 VDC):
204 mA - Minimum Display Module
232 mA - Standard Display Module
232 mA - Command Display Module
Detector Module (at 24 VDC):
260 mA - fan speed 1
380 mA - fan speed 6 (default speed)
940 mA - fan speed 16
Detection: Principle: Laser light scattering mass detection and particle evaluation
Particle sensitivity range: 0.003 to 10 microns
Sampling pipe: Length: Up to 250 m (820 ft.) combined per detector module
Quantity sampling holes: Up to 20 - Class A per detector module; Up to 40 - Class B per detector module; Up to 50 - Class C per detector module
Inlet size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
Inlet location: Top or bottom
Exhaust size: 27 or 25 mm (1.06 or 0.98 in) outer diameter
Exhaust location: Top or bottom
Inlet quantity: 1 per detector module
Input: Quantity: 2 per module
Type / rating: Supervised
Termination: 15 KΩ 5% 1/4 W
Programmable: Yes
Output: Quantity: 3 per module
Type / rating: Voltage free (contact rating 2 A at 30 VDC / NO/NC/C)
Programmable: Yes
Colour: Cream
Mounting type: Surface
Cable entries: 2 at the bottom,​ 2 at the rear,​ 2 at the top on Detector Module,​ and 3 at the top on the Display Module
Cable entry size: 20 mm (0.5 in) - top and bottom
Detector module orientation: Vertical (0 deg or 180 deg)
Operating temperature: Equipment: -20 to +60 °C (-4 to +140 °F)
Sampled air: -20 to +60 °C (-4 to +140 °F)
Relative humidity: 0 to 95% non-condensing
IP rating: IP40, indoor
Chart recorder: Sampling period: Adjustable between 1s and 60 s
Capacity: 1 month @ 1s / Up to 5 years @ 60 s
Values recorded: Detector value,​ 4 alarm level values,​ flow value and temperature (all simultaneously)
Compatible products: 9-30780: AirSense ModuLaser, Minimum Display Module
9-30781: AirSense ModuLaser, Standard Display Module
9-30783: AirSense ModuLaser, Detector Module
Regulatory: REACH,​ RoHS compliant
BOSEC,​ CPR,​ CSIRO,​ EN54-20,​ LPCB,​ VdS certified
Weight: Display Module: 1.18 Kg (2.6 lb.)
Detector Module: 1.57 Kg (3.46 lb.)