SKU
EXP-006
£57.50
£47.92
Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
Available on Backorder
This item is not currently in stock, but it is available to backorder. Contact us for lead time.
Product Details for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
The Advanced EXP-006 Zone Active end-of-line Module provides active end-of-line monitoring for zone circuits fitted with detector diode bases in accordance with BS5839-1 Clause 12.2.2f.
The normal 6800Ω end-of-line resistor supplied with the panel is not used. The module will create an open circuit condition on the panel if a detector is removed from its base.
Key Features of the EXP-006 |
|---|
|
> Provides monitoring for zone circuits fitted with detector diode bases
> Creates an open circuit condition on the panel if a detector is removed from its base > Normal 6800Ω end-of-line resistor supplied with the panel is not used > Refer to panel manuals for details of the number of detectors that can be connected to the zone circuit |
| Brand | Advanced Electronics |
|---|---|
| Manufacturer Part No. | EXP-006 |
| Product Series | ExGo |
| Primary Power Source | 24V DC |
| System Type | Conventional |
| Warranty | 3 Years |
Write Your Own Review
FAQ’s for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
No questions yet. Be the first to ask the question!
Product Specification for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
| Product Code: | EXP-006 |
| Product description: | Zone Active end-of-line Module |
| Dimensions: | W:20mm x H:27mm x D:7mm (max) |
| End-of-line resistance: |
6800 Ohms |
| Humidity: | 95% max |
| Environmental class: |
Indoor -5oC to +40oC |
| Operating voltage: |
17 - 30V DC |
| Zone voltage: |
20V DC typical |
| Current consumption (fault condition): |
40μA typical |
| Compatibility: |
ExGo Series Gas Extinguishing Panel input circuits |
| Limitations: |
For use in gas extinguishing installations where an EOL module is required |