Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

SKU
EXP-006
£57.50 £47.92
Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
Available on Backorder This item is not currently in stock, but it is available to backorder. Contact us for lead time.

Product Details for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

The Advanced EXP-006 Zone Active end-of-line Module provides active end-of-line monitoring for zone circuits fitted with detector diode bases in accordance with BS5839-1 Clause 12.2.2f.

The normal 6800Ω end-of-line resistor supplied with the panel is not used. The module will create an open circuit condition on the panel if a detector is removed from its base.


Key Features of the EXP-006

> Provides monitoring for zone circuits fitted with detector diode bases
> Creates an open circuit condition on the panel if a detector is removed from its base
> Normal 6800Ω end-of-line resistor supplied with the panel is not used
> Refer to panel manuals for details of the number of detectors that can be connected to the zone circuit

More information about Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

More Information
Brand Advanced Electronics
Manufacturer Part No. EXP-006
Product Series ExGo
Primary Power Source 24V DC
System Type Conventional
Warranty 3 Years
Write Your Own Review
You're reviewing:Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)
Your Rating

Datasheets and Manuals for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

FAQ’s for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Advanced ExGo Spare Zone Active End-Of-Line Module (Pack of 5) (EXP-006)

Product Code: EXP-006
Product description: Zone Active end-of-line Module
Dimensions: W:20mm x H:27mm x D:7mm (max)
End-of-line resistance:
6800 Ohms
Humidity: 95% max
Environmental class:
Indoor -5oC to +40oC
Operating voltage:
17 - 30V DC
Zone voltage:
20V DC typical
Current consumption (fault condition):
40μA typical
Compatibility:
ExGo Series Gas Extinguishing Panel input circuits
Limitations:
For use in gas extinguishing installations where an EOL module is required