Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

SKU
EXP-005
£82.56 £68.80
Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)
Available to Order This item is not currently in stock at our main warehouse, but it is available to backorder or may be sent directly from the manufacturer. Contact us for lead time.

Product Details for Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

The Advanced EXP-005 switch module provides a simpler way of correctly terminating the switch input circuits of the ExGo Series Extinguishing Control Panel/System. The module consists of a printed circuit card and connector.


Key Features of the EXP-005

> Switch EOL module
> Pack of 5
> ExGo control equipment

More information about Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

More Information
Brand Advanced Electronics
Manufacturer Part No. EXP-005
Product Series ExGo
Primary Power Source 24V DC
System Type Conventional
Warranty 3 Years
Write Your Own Review
You're reviewing:Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)
Your Rating

Datasheets and Manuals for Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

FAQ’s for Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

Loading...

 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!

Product Specification for Advanced ExGo Switch End-Of-Line Module (Pack of 5) (EXP-005)

Product Code: EXP-005
Product description: ExGo Switch End of Line Module
Dimensions:
Overall
PCB

W:27mm x H:38mm x 15mm
W:20mm x H:27mm x D:2mm
End-of-line resistance:
6800 Ohms
Humidity: 95% max
Environmental class:
Indoor -5oC to +40oC
SW#1 active resistance:
470 Ohms general input - switch; valve input - closed switch
SW#2 active resistance:
6800 Ohms general inputs - not used; valve input - open switch
Max. operating voltage:
30V DC
Compatibility:
ExGo Series Gas Extinguishing Panel input circuits
Limitations:
For use in gas extinguishing installations where an EOL module is required