SKU
MXP-547-BX
£991.55
£826.29
Advanced MXP-547-BX MxPro 5 ESPA Pager Interface (Boxed)
Available on Backorder
This item is not currently in stock, but it is available to backorder. Contact us for lead time.
Product Details for Advanced MxPro 5 ESPA Pager Interface (Boxed) (MXP-547-BX)
The Pager Interface is a programmable interface providing connectivity of third party paging systems to the MxPro 5 control equipment. It utilises the industry standard protocol ESPA 4.4.4 and connects to the equipment via a serial data connection. An optional input function is available to monitor pager fault conditions. Specific event types (e.g. Fire, Alarm, Pre- Alarm, Fault, etc.) can be sent to individual pagers and/or to groups of pagers.
For use with pager systems compliant to ESPA 4.4.4 protocol. If a printer is also required, fit an internal printer assembly.
Key Features of the MXP-547-BX |
|---|
|
> Up to 8 configurable shifts per weekday/weekend
> Up to 50 pager groups > Up to 250 pager addresses > Each pager address can be configured to cover 2 zone ranges > Zone and/or point information can be sent to the pager > User defined texts are available and the basic event type text can be configured > ESPA 4.4.4 protocol > Panel mounted or boxed version > Easily configured via pager PC Software > 3 year warranty as standard > Boxed |
| Brand | Advanced Electronics |
|---|---|
| Manufacturer Part No. | MXP-547-BX |
| Product Series | MxPro 5 |
| Primary Power Source | 24V DC |
| System Type | Addressable |
| Warranty | 3 Years |
Write Your Own Review
FAQ’s for Advanced MxPro 5 ESPA Pager Interface (Boxed) (MXP-547-BX)
No questions yet. Be the first to ask the question!
Product Specification for Advanced MxPro 5 ESPA Pager Interface (Boxed) (MXP-547-BX)
| Power Supply | 15-30V DC (e.g. wired from panel 24V auxiliary supply) |
| Supply Current | 100mA (typical at 24V DC) |
| Temperature | -5°C to 50°C |
| Humidity | 95% humidity (non condensing) |
| Dimensions H x W x Dmm | Enclosure: 218 x 300 x 45 |
| Pager Interface | RS232 galvanically (opto) isolated |
| Fault Input | Non-monitored/monitored (10K EOL, 470R active) |
| Event Types Supported | Fire Alarm, Test Alarm, Plant Alarm, Pre-Alarm, Fault and Disablement |