Nittan evo+5802 2-8 Loop Fire Panel c/w 2 Loop Cards - Standard Network

SKU
evo+5802
£4,831.08 £4,025.90
Nittan evo+5802 2-8 Loop Fire Panel c/w 2 Loop Cards - Standard Network
  • Buy 10 for £4,793.04 £3,994.20 each and save 1%
  • Buy 20 for £4,755.00 £3,962.50 each and save 2%
  • Buy 40 for £4,716.96 £3,930.80 each and save 2%

The Nittan evo+5802 is a 2-8 loop addressable fire alarm panel fitted with 2 loop cards for Nittan Evolution protocol and a standard network card.

The evo+5800 series is fully expandable from 2 to 8 loops and supplied with 8 on-board sounder circuits, 20 programmable zonal LEDs with slide-in labels, and 25 System LEDs for information purposes. There are also 4 programmable function buttons with LED indication for confirmation of operation.

The control panel consists of the latest dual flash-based microprocessor technology combined with a high resolution, high contrast, graphical LCD display and tactile keypad providing a simple ‘select and click’ programming aid for engineer configuration and end-user operation.

Powerful cause-and-effect programming coupled with dynamic zoning and enhanced trace diagnostics makes the panel suitable for a wide range of site applications from small to large complex multi-area systems. Fully programmable onsite via the on-board alphanumeric keypad, or PC-NeT configuration software.

PC Software

An extensive suite of user-friendly Windows based PC software programs has been developed to enhance your experience when using evo+5800 series fire panels. The suite incorporates a number of different programmes to include a configuration, service, logo and virtual panel tool to allow the flexibility of the equipment to be fully explored.

Network

Simply adding a network card allows the panel to communicate with any other evo+ fire panel, remote terminal, or network peripheral, such as, ipGateway™ or BMS/graphical interface. The network operates as a true peer-to-peer system and can be configured in a fault-tolerant loop or radial format.


Key Features
> c/w 2 Loop Cards fitted (expandable up to 8 loops with additional loop cards)
> c/w Standard Network Card
> 20 programmable Zonal / 25 System LEDs
> Nittan Evolution protocol
> Graphical LCD user interface and support for up to 200 fire zones by default allowing full EN54 compliance without additional hardware
> Dedicated USB & RS232 serial port for direct PC or modem connection
> Installer friendly Auto-learn, Loop Detection and Onboard Scope facility for ease of commissioning and fault finding
> The graphical display can be configured to operate with virtually any language or character set
> Integral P-Bus for system expansion via available option cards
> Ad-NeT peer-to-peer network with up to 2000 zones
> Approved to BS EN54 part 2 and 4
> Robust removable equipment chassis with plug-in connectors for simple fixing and cable termination
More Information
ManufacturerNittan
MPNF12N95802
Write Your Own Review
You're reviewing:Nittan evo+5802 2-8 Loop Fire Panel c/w 2 Loop Cards - Standard Network
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Base TechnologyDual flash-based processors with real-time clock, trace diagnostics, programmable languages and character sets
DisplayWhite backlit 240 x 64 graphical LCD
LED Indicators22 red (1 x Fire, 1 x More Alarms, 20 x Zonal Programmable), 1 green (Power), 13 amber and 12 bi-colour (Fault & System)
ControlsAlpha numeric keypad permitting navigation, Reset, Mute, Silence, Resound, Evacuate, and 4 x Programmable push buttons
ProtocolsNittan Evolution
Number of Fire Zones2000 (200 per individual panel)
Number of LoopsDedicated 2-8 loop control panel
Devices per LoopMax 254
Loop Current500mA per loop
On-Board Sounder Circuits8 x 1 Amp programmable
On-Board Relays 4 x 1 Amp 30v AC/DC programmable(10mA, 5v min) - expandable to 8 using 2 x Mxp-507
Auxiliary Supply2 x 24v 500mA 2
Programmable Input2 x monitored programmable input on-board
Programmable Key Switch Inputs16 volt free inputs
Total Available Output Current2 x 5A maximum available for loop current + sounder outputs + auxiliary supply
Mains Supply200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4A Max
Battery Capacity2 x 24V 4Ah internal (min), 2 x 24V 18Ah internal (max),
or 1 x 24v 45Ah internal (max) and 1 x 24v, 45Ah external (max)
Charger Current2 x 2A temperature compensated
Serial Port2 x on-board RS232 connection for PC, modem, IP, or portable printer
USB Interface2 x USB B type connection for PC communication
ProgrammingOn-board keypad or PC running Windows tools
Event Log2 x 5000 event & diagnostic + 500 fire
NetworkingOptional plug-in network card (Mxp-503 - standard, or Mxp-509 - fault-tolerant)
Printer (optional)On-board
Enclosure / ColourSteel IP30 / RAL7035
Cable Entry (20mm knockouts)30 x top, 6 x rear, 3 x bottom, plus 2 x double knockout rear
Size H x W x D mm750 x 450 x 190
Metalwork OptionsSemi-flushing bezel, battery box, utility enclosure, termination enclosure and rack mount
ApprovalsEN 54-2:1998, EN 54-4:1998, EN 54-13:2005
Nittan evo+5802 2-8 Loop Fire Panel c/w 2 Loop Cards - Standard Network