Apollo XP95 A2S 55°C Heat Detector - 55000-400APO

SKU
55000-400APO
£31.70 £26.42
Apollo XP95 A2S 55°C Heat Detector - 55000-400APO
  • Buy 10 for £30.94 £25.78 each and save 2%
  • Buy 20 for £30.70 £25.58 each and save 3%
  • Buy 50 for £30.44 £25.37 each and save 4%

The XP95 Heat Detector monitors temperature by using a single thermistor which provides a count output proportional to the external air temperature. The XP95 range features two heat detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C.

Operation

The XP95 heat detectors have a low air flow resistance case made of self-extinguishing white polycarbonate. 

The devices monitor heat by using a single thermistor network which provides a voltage output proportional to the external air temperature. 

The standard heat detectors, 55000-400 and 55000-420, respond to increasing air temperature in such a way that they are classified as an A2S device. Both devices will give 55 counts at 55°C.

Watch the Video

Electrical Description

The detectors are designed to be connected to a two wire loop circuit carrying both data and a 17V to 28V dc supply. 

The detectors are connected to the incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between +R and -R terminals. An earth connection terminal is also provided. 

When a device is energised the ASIC regulates the flow of power and controls the data processing. The thermistor provides an output over normal operating ranges that is proportional to the external air temperature. This voltage output is processed in the A/D converter and stored by the communications ASIC. It is transmitted to control equipment when the device is interrogated. When a count of 55 is exceeded the alarm flag is initiated and the device address is added to the data stream every 32 polling

 

Device Addressing

Each XP95 device responds to interrogation and command from central control equipment. It communicates to the panel information on status, command bits, type, location, and other information that allows an alarm to be raised even when the device is not itself being interrogated. Message error checking is also provided. The devices are compatible with Discovery® systems and control equipment to aid maintenance, extension and upgrade of existing systems.

A unique, patented XPERT card provides simple, user friendly and accurate identification of detector location whereby a coded card, inserted in the base, is read by any detector once it is plugged in. All the electronic components are in the detector but the location information is held in the base. The address card simplifies and speeds up installation and commissioning. Addressing errors during maintenance and service are eliminated.

The XP95 detectors provide an alarm facility that automatically puts an alarm flag on the data stream and reports its address when the pre-set EN54 thresholds are exceeded. The devices provide great flexibility in system design with the control equipment determining the characteristics of the system. A large and growing range of compatible control equipment is available from many sources - details are available from Apollo on request.

 

Mounting Bases are sold separately


Key Features
> Designed to trigger when a temperature of 55°C has been reached
> Ideal in environments that are dirty or smoky under normal conditions
> Well-suited to warehouses, loading bays and car parks
> Unaffected by wind or atmospheric pressure
> Alarm flag for fast alarm reporting
> Alarm address for fast location of alarm
> XPERT 7 Card addressing
> Electronics-free base (sold separately)
> Easy installation
> Elegant design
> Mounting Bases are sold separately
More Information
ManufacturerApollo Fire Detectors
MPN55000-400APO
Write Your Own Review
You're reviewing:Apollo XP95 A2S 55°C Heat Detector - 55000-400APO
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Specifications are given at 23°C and 50% relative humidity unless stated otherwise.
Product Code:55000-400APO
Detector Type:Point type heat detector for fire detection and fire alarm systems for buildings
Detector Principles:Linear approximation over temperature range 25°C to 90°C
Sensor:Single NTC Thermistor
Sampling Frequency:Continuous
Sensitivity:25°C to 90°C: 1°C/count. - -20°C returns 8 counts
Supply Wiring:Two wire supply, polarity insensitive
Supply Voltage:17 to 28 Volts DC
Modulation Voltage at Detector:5 to 9 Volts peak to peak
Quiescent Current:250μA average, 500μA peak
Power-up Surge Current:1mA
Duration of Power-up Surge Current:0.3 seconds
Maximum Power-up Time:4 seconds
Analogue Value at 25°C:25±5 Counts
Alarm Level 55 Counts:55°C when measured under static conditions
Alarm Indicator:Red light emitting diode (LED)
Alarm LED Current:2mA
Remote LED Current:4mA at 5V
Storage Temperature:-30°C to +80°C
Operating Temperature:-20°C to +70°C
Humidity: 0% to 95% relative humidity
Wind SpeedUnaffected in fixed temperature use
Atmospheric Pressure:Unaffected
Vibration, Impact & ShockTo EN54-5:2000
IP Rating:53
Dimensions (D x H): 100 x 42mm (100 x 50mm in Base)
Weight:105g (157 in Base)
Materials:Detector Housing: White polycarbonate V-0 rated to UL94 - Terminals: Nickel plated stainless steel