Nittan EV-OP Relay Interface Output Module

SKU
EV-OP
£70.10 £58.42
Nittan EV-OP Relay Interface Output Module
  • Buy 10 for £69.55 £57.96 each and save 1%
  • Buy 20 for £69.00 £57.50 each and save 2%
  • Buy 40 for £68.45 £57.04 each and save 2%

The Nittan EV-OP Relay Interface Module provides one volt-free relay changeover contact on a latching relay. The relay is controlled by a command sent from the Evolution fire panel via the addressable loop. The relay state (activated, deactivated or stuck) is returned to the controller.

Address Programming

The Nittan EV-OP must have its Loop Address programmed prior to installation with the EV-AD2 Programmer, using the Universal Addressing Lead (Two Pin) supplied with the EV-AD2 kit, by connecting Red pin to L+ & Black pin to L- on the reverse of the device. You can also use the EV Module Addressing Lead (Three Pin) via the Programming Port in the front cover (See Fig.2), after the device is installed.

The module must not be used to switch mains voltages


Key Features
> Addressable functionality - The control panel sends a command to operate the relay, then reports an activated or deactivated state back to the panel through the use of a set of contacts dedicated to monitor the state of the relay
> One volt-free dry contact relay output
> LED status indicator which is normally off. When the EV-OP receives a command to activate, the LED lights
> EEPROM Addressed (Programmer)
> Housing fits MK 2 gang pattress box
> Control Output for EV-240V MRA
More Information
ManufacturerNittan
MPNEV-OP
Write Your Own Review
You're reviewing:Nittan EV-OP Relay Interface Output Module
Your Rating
Loading...

Sort By: 

Ask Question

All questions will be displayed after moderation.

No questions yet. Be the first to ask the question!
Type Identification Value49
System CompatibilityUse only with Evolution Fire Alarm Panels (CIE) which support this unit
Loop Voltage20 - 38 Vdc
EnvironmentIndoor Application only
Operating Temperature-25° to +70°C
Storage Temperature-40° to +80°C
Operating HumidityUp to 95% non-condensing
Dimensions (HWD)87 x 148 x 14mm
Mounting RequirementsOne MK dual gang backbox surface mount
Wire SizeMin 1.5mm2
Max 2.5mm2
Battery RequirementsStand-by current: 0.46mA max
Alarm current: 4.5mA max
Addressable Device Conditions• Normal
• Output Active
• Device Type invalid
• Device No Response
• Output Stuck
Relay Contact RatingDC - 2A @ 24V dc
Declaration of Performance00114
Nittan EV-OP Relay Interface Output Module